| 2005-07-11 00:00:00 | ************ UNSAT ************ |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE NEW NOTES. |
| | |
| | **************************************** |
| | PLEASE SEE A RESPONSE LETTER WOULD HELP |
| | IN THE REVIEW PROCESS IN ORDER TO |
| | CLARIFY CERTAIN CODE ITEMS. |
| | |
| | **************************************** |
| | |
| | |
| | 1)NOTE: PLEASE PROVIDE ALL LIGHT POLE/ |
| | LIGHT FIXTURE WIND LOADING INFORMATION |
| | FOR REVIEW AT THIS TIME. |
| | PLEASE SEE MIN FBC 140 MPH. |
| | IF "SITE LIGHTING" WIND LOAD INFORMATION |
| | AND FIXTURE INFORMATION IS NOT PROVIDED |
| | AT THIS TIME, A SEPARATE PERMIT MAY BE |
| | APPLIED FOR AT A LATER DATE. |
| | |
| | 2)NOTE:PLEASE SEE FAC 61G15-23.002 FOR |
| | MISSING INFORMATION REQUIRED ON TITLE |
| | BLOCK FOR ENG FIRM. PLEASE ALSO SEE FS |
| | 471.023. |
| | PLEASE SEE THIS INFORMATION IS REQUIRED |
| | ON ALL SHEETS AND FOR ALL TRADES |
| | WHEATHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 3)NOTE:PLEASE SEE NOTES FOR ELECTRICAL |
| | REFERENCES SOME CODES FROM THE 1996 NEC. |
| | PLEASE SEE WE ARE CURRENTLY UNDER THE |
| | 2002 NEC. |
| | |
| | 4)NOTE: PLEASE SEE 3.03, A "PANEL" IS |
| | SHOWN BUT NO INDICATION OF WHAT PANEL |
| | IS. |
| | |
| | 5)NOTE: PLEASE NOTE ON LIGHTNING |
| | PROTECTION PLANS FOR ALL WORK TO BE |
| | INSTALLED PER NFPA-780. |
| | |
| | 6)NOTE: PLEASE SUBMIT ALL INFORMATION ON |
| | FIRE PUMP/ FIRE PUMP CONTROLLER. |
| | PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| | FOR BOTH. |
| | PLEASE SEE NO SUBMITTIALS/SPECS/ CUT |
| | SHEETS COULD BE LOCATED. |
| | PLEASE SEE 230.76,230.79 FOR THE |
| | REQUIRED MANUAL MEANS OF DISCONNECT |
| | REQUIRED. PLEASE SPECIFY THIS ON PLANS. |
| | PLEASE PLACE NOTE ONRISER DIAGRAM |
| | THAT THE OVERCURRENT PROTECTIVE |
| | DEVICE(S) SHALL BE SELECTED OR SET TO |
| | CARRY INDEFINITELY THE SUM OF THE |
| | LOCKED-ROTOR CURRENT OF THE FIRE PUMP |
| | MOTOR(S) AND THE PRESSURE MAINTENANCE |
| | PUMP MOTOR(S) AND THE FULL-LOAD CURRENT |
| | OF THE ASSOCIATED FIRE PUMP ACCESSORY |
| | EQUIPMENT WHEN CONNECTED TO THIS POWER |
| | SUPPLY. |
| | PLEASE SEE MISSING CONDUCTORS FROM FIRE |
| | PUMP CONTROLLER TO FIRE PUMP. |
| | PLEASE SEE FEEDER #9 SHOWS AN |
| | EQUIPMENTGROUNDING CONDUCTOR FROM FPL TO |
| | FIRST MEANS OF DISCONNECT. PLEASE SEE |
| | 250.6,250.24, EQUIPMENT GROUNDS ARE ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 7)NOTE: PELASE SEE 445.13 FOR SIZING OF |
| | CONDUCTORS FROM GENERATOR.THE AMPACITY |
| | OF THE CONDUCTORS FROM THE GENERATOR |
| | TERMINALS TO THE FIRST DISTRIBUTION |
| | DEVICE(S) CONTAINING OVERCURRENT |
| | PROTECTION SHALL NOT BE LESS THAN 115 |
| | PERCENT OF THE NAMEPLATE CURRENT RATING |
| | OF THE GENERATOR. |
| | |
| | 8)NOTE: PLEASE SEE FEEDER #28 ON FEEDER |
| | SCHEDULE, PLEASE CALRIFY # OF |
| | CONDUCTORS? |
| | |
| | 9)NOTE: PLEASE INDICATE INFORMATION FOR |
| | GENERATOR, GENERATOR SIZE ETC. |
| | PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| | FOR GEN/ ATS/ GEN SUB-BASE FUEL TANKS |
| | ETC. |
| | PLEASE SEE ATS FEED AND OCP IS SHOWN AS |
| | 100A'S,, HOWEVER LOAD SHOWN EXCEEDS |
| | RATING OF BRKR AND ATS. |
| | PLEASE SHOW SIZING OF CONDUCTORS PER |
| | ABOVE. |
| | PLEASE SEE MISSING OCP AT GENERATOR>? |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE SEE 695.3, THE MAIN FOR |
| | FIRE PUMP SHOULD NOT BE LOCATED IN THE |
| | SAME ROOM AS NORMAL MAINS. PLEASE SEE IF |
| | THERE WAS A FIRE OF SORTS IN MAIN |
| | ELECTRICAL RM OR EQUIPMENT THIS WOULD |
| | DIRECTLY AFFECT ELECTRICAL POWER TO FIRE |
| | PUMP. |
| | |
| | 11)NOTE: PLEASE CORRELATE CIRCUTING FOR |
| | RECEPTS IN ELEC/MACH/ELEV RMS WITH 1/4" |
| | SCALE ON EACH SHEET WITH SAME RECEPTS |
| | SHOWN ON PLANS. |
| | 215.5 |
| | |
| | 12)NOTE: PLEASE SEE NOTE #1 ON E4.10 |
| | ELECTRICAL NOTES MENTIONS, "MAIN CIRCUIT |
| | BREAKERS IN PANEL BOARDS SHALL BE GROUND |
| | FULAT PROTECTED" |
| | PLEASE VERIFY THIS ? PLEASE SEE |
| | 240.13,230.95 ETC WHEN GROUND FAULT |
| | PROTECTION IS REQUIRED. THIS IS STILL IN |
| | QUESTION. PLEASE EXPLAIN IN RESPONSE |
| | LTR. |
| | |
| | 13)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | REQUESTED ON PREVIOUS REVIEW. |
| | |
| | 14)NOTE: PLEASE SHOW OR NOTE ALL TRACK |
| | LIGHTING CALCULATIONS PER 220.12 |
| | REQUESTED ON PREVISOU REVIEW. |
| | |
| | 15)NOTE: PLEASE SEE NOTE #22 ON E0.03 |
| | FOR |
| | |
| | 16)NOTE: PLEASE SEE 700.16 AND 620.23A, |
| | 620.24 FOR REQUIREMENTS IN ELEC RMS/ |
| | ELEVATOR MACHINE RMS ETC. |
| | PLEASE SEE THIS WAS REQUESTED ON |
| | PREVIOUS REVIEW, HOWEVER NO CHANGES SEEM |
| | TO HAVE BEEN MADE. A SEPARATE BRANCH |
| | CIRCUIT SHALL SUPPLY THE MACHINE ROOM OR |
| | CONTROL ROOM/MACHINERY SPACE OR CONTROL |
| | SPACE LIGHTING AND RECEPTACLE(S). |
| | |
| | 17)NOTE: PLEASE PROVIDE ALTERNATING |
| | CIRCUITING FOR ALL EGRESS AREAS. |
| | ALTERNATING CIRCUITING IS ALREADY SHOWN |
| | FOR STAIRWELLS.LS 101 7-9 |
| | EMERGENCY LIGHTING SYSTEMS SHALL BE |
| | DESIGNED AND INSTALLED SO THAT THE |
| | FAILURE OF ANY INDIVIDUAL LIGHTING |
| | CIRCUIT, SUCH AS THE BURNING OUT OF A |
| | LIGHT BULB,TRIPPING OF A BREAKER OR |
| | TURNING OFF OF A SWICTH CANNOT LEAVE IN |
| | TOTAL DARKNESS ANY SPACE THAT REQUIRES |
| | EMERGENCY ILLUMINATION. |
| | WHERE HIGH-INTENSITY DISCHARGE LIGHTING |
| | SUCH AS HIGH- AND LOW-PRESSURE SODIUM, |
| | MERCURY VAPOR, AND METAL HALIDE IS USED |
| | AS THE SOLE SOURCE OF NORMAL |
| | ILLUMINATION, THE EMERGENCY LIGHTING |
| | SYSTEM SHALL BE REQUIRED TO OPERATE |
| | UNTIL NORMAL ILLUMINATION HAS BEEN |
| | RESTORED. |
| | |
| | 18)NOTE: PLEASE SEE PLANS ARE INDICATING |
| | BLDG AS "HISTORIC" YET IT IS UNCLEAR IF |
| | BUILDING HAS "HISTORIC DESIGNATION"? |
| | THIS IS ONLY NOTED: |
| | |
| | PLEASE SEE POSSIBLE NOTES FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SEE THERE MAY BE FURTHER COMMENTS |
| | SINCE NOT ALL INFORMATION WAS SUBMITTED |
| | FOR REVIEW. |
| | |
| | PLEASE REVMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STMAPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2005-07-08 00:00:00 | IN ELEC FOR REVIEW. |