| 2007-06-09 18:50:31 | ** UNSAT ** |
| | SHEETS E 2.02, 2.02C, 4.10 AND 5.01 HAVE COMMENTS. ALL |
| | OTHER SHEETS STAMPED AS REVIEWED. |
| | |
| | 1) NOTE: PLEASE SEE PHOTO-METRICS ON WEST SIDE OF |
| | BUILDING DOES NOT INDICATE THE ENTIRE EGRESS PATH ON |
| | STAIRS FOR POINTS CALCULATED. THE AREA BY THE HAND |
| | RAILS IS ONLY PART OF THE STAIRS. |
| | PLEASE SEE LS 101 7.8.1.3, 7.9.2. |
| | PLEASE SEE THE CIRCUITING ON PLANS INDICATES EM-1, YET |
| | EM-1 ON PANEL SCHEDULE DOES NOT COORDINATE WITH THIS. |
| | ALL THREE STAIRS ARE NOTED WITH THE SAME EM-1. |
| | PLEASE REVISE E2.02, 2.02C. |
| | |
| | 2) NOTE: PLEASE SEE RISER WHICH INDICATES MDH AS |
| | 900AMPS WHICH THE CONDUCTORS AS SHOWN ON SCHEDULE WOULD |
| | NOT MEET 240.4C |
| | PLEASE SEE SHEET 5.01 AS THIS SHOWS AN 800AMP BUS AND A |
| | 700AMP MAIN? |
| | PLEASE BE SURE TO COORDINATE THIS MAIN AND ANY OTHERS |
| | BEFORE SUBMITTING REVISIONS. |
| | |
| | 3) NOTE: AS NOTED, PLEASE SEE THE GROUNDING DETAIL ON |
| | 5.10 WHICH INDICATES *FENCE STEEL AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM AT CHILLER PLANT. THIS SEEMS |
| | TO BE A MISPRINT. THIS WAS CONFIRMED WITH GC |
| | SUPERINTENDENT THAT THIS IS THE FOOTER STEEL. THIS WAS |
| | REDLINED ON THIS SHEET AND STAMPED. |
| | |
| | |
| | **OTHER PLAN SHEETS SUBMITTED STAMPED. |
| | |
| | ** IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |