| 2005-03-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY CODE W.P.B. |
| | |
| | 1) ALL SHEETS SHALL BE SIGNED, SEALED, & |
| | DATED. ALL SHEETS SHALL CONTAIN A TITLE |
| | BLOCK WITH ALL REQUIRED INFORMATION AND |
| | LICENCES. FAC 61G1-16.004 - |
| | 61G14-23.002(2) AND FS 481.219 - |
| | 481.2055 - 471.025. |
| | 2) SHT C2 CONDENSATE WATER SHALL NOT |
| | DRAIN INTO THE SANITARY SEWER SYSTEM. |
| | THE CONDENSATE SHALL DRAIN SEPARATELY |
| | OUT OF THE BUILDING AND SHALL CONNECT TO |
| | A STORM LINE, CATCH BASIN, OR DRYWELL. |
| | CITY CODE 90-125(B)(5). A RELIEF VENT IS |
| | REQUIRED ON CONDENSATE LINE AS IT EXITS |
| | THE BUILDING. |
| | 3) SHT A-1.05 SECONDARY ROOF DRAINS FOR |
| | THE EAST SIDE OF THE BUILDING ARE NOT |
| | SHOWN. PLEASE INDICATE THE LOCATION AND |
| | SIZE. SECTION 1107. |
| | 4) SHT A-1.06 SCUPPER DETAIL (2) PLEASE |
| | INDICATE WIDTH AND HEIGHT DIMENSIONS TO |
| | DETERMINE AREA. SECTIONS 1107 & 104.2.1. |
| | 5) SHT A-6.09 THE FOLLOWING INFORMATION |
| | IS MISSING FROM THE ACCESSIBILITY |
| | REQUIREMENTS. SHOW: CLEAR FLOOR SPACE |
| | FOR THE URINAL 11-4.18.3. - CLEAR FLOOR |
| | SPACE FOR THE LAV OUTSIDE THE STALL FOR |
| | PERSONS USING THE ACCESSIBLE URINAL |
| | 11-4.19.3. - EXPOSED PIPES AND SURFACES |
| | 11-4.19.4. - ALL ACCESSIBLE W/C'S SHALL |
| | BE 18" FROM CENTERLINE OF FIXTURE TO THE |
| | WALL. SEE FIG. 29. |
| | 6) SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH 11-4.15.2 SPOUT HEIGHT, 11-4.15.3 |
| | SPOUT LOCATION, 11-4.15.4 CONTROLS, AND |
| | 11-4.15.5 CLEARANCES/CLEAR FLOOR SPACE. |
| | ALSO FOR THOSE WHO HAVE DIFFICULTY |
| | BENDING OR STOOPING SECTION |
| | 11-4.1.3(10)(A). |
| | 7) SUBMIT A DETAIL FOR THE BREAK ROOM |
| | SINKS AND THE CONFERENCE ROOM SINK |
| | SHOWING COMPLIANCE WITH 11-4.24 AND ALL |
| | SUBSECTIONS. CLEAR FLOOR SPACE SHALL BE |
| | FORWARD APPROACH AND EXTEND A MAXIMUM OF |
| | 19" UNDERNEATH THE SINK. CABINET DOORS |
| | SHALL NOT BE IN THE CLEAR FLOOR SPACE |
| | FOR THE SINKS. REMOVE DOORS |
| | 8) SHT A-6.10 DERTAILS 2, & 3. W/C'S TO |
| | BE 18" OFF WALL TO CENTERLINE OF THE |
| | FIXTURE. FIG. 29. |
| | 9)SHT A-9.06 DETAIL #10 29" KNEE |
| | CLEARANCE REQUIRED. DETAIL SHOWS 26". |
| | 10) SHT P-2.01 CENTER RWL'S (2) FOR EAST |
| | SIDE OF ROOF MISSING. SHOW LOCATION FOR |
| | BOTH. SECTION 104.2.1. |
| | 11) SHT P-2.02 NO SANT. SHOWN TO THE W/C |
| | IN THE ACCESSIBLE STALL IN THE WOMEN'S |
| | TOILET ROOM. SECTION 104.2.1. |
| | 12) SUBMIT RISER DIAGRAMS FOR THE |
| | SANITARY, THE STORM, WATER, & |
| | CONDENSATE. SECTION 104.2.1. |
| | 13) SUBMIT BUILDING DRAIN ISOMETRICS FOR |
| | THE SANITARY, (SHOWING DFU'S AS THEY |
| | ACCUMULATE), THE STORM, (SHOWING SQUARE |
| | FOOTAGE AS IT ACCUMULATES), AND |
| | CONDENSATE. SHOW ALL PIPE SIZES. |
| | 14) SUBMIT A WATER ISOMETRIC SHOWING ALL |
| | PIPE SIZES, VALVES, AND WATER HAMMER |
| | ARRESTORS LOCATED NEAR THE FIXTURES IN |
| | AN "EFFECTIVE RANGE" PER PDI-WH 201. |
| | 15) SHT P-5.02 SUBMIT MANUFACTURE |
| | SPECIFICATION SHEETS FOR DOMESTIC |
| | BOOSTER PUMP SHOWING LISTING. |
| | 16) SINCE ARCHITECTURAL PLANS ARE 75% |
| | FINISHED, AND PLUMBING PLANS ARE 50% |
| | FINISHED, MORE NEW COMMENTS MAY FOLLOW |
| | NEXT REVIEW. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |