| Date |
Text |
| 2005-04-06 00:00:00 | DENIED: |
| | 1.PLAN SHEET M-2.01 - FIRE DAMPERS ARE |
| | NOT INDICATED AT THE FOLLOWING |
| | LOCATIONS; ROOM #108, 134, 113, 122 AND |
| | VARIOUS PENETRATIONS INTO THE CORRIDOR. |
| | PLEASE NOTE THE FOLLOWING: |
| | A) SOME DUCT PENETRATIONS INTO THE |
| | CORRIDOR MAY NOT REQUIRE FIRE |
| | FIRE DAMPERS BUT MUST COMPY WITH |
| | 2001 FBC/M 607.1.3, EXCEPTION #3 |
| | ITEMS 1 THROUGH 4. |
| | B) 2001 FBC 1006.1.3, PENETRATIONS INTO |
| | |
| | & OPENINGS THROUGH A STAIRWAY |
| | ENCLOSURE ARE PROHIBITED. |
| | C) SPECIFIC LOCATION OF EACH FIRE |
| | DAMPER SHALL BE IDENTIFIED ON THE |
| | PLAN PER 2001 FBC/M 607.6. |
| | |
| | 2.PLAN SHEET M-2.02 - FIRE DAMPERS NOT |
| | INDICATED AT THE FOLLOWING LOCATIONS; |
| | CORRIDORS AT THE FOYER, ROOM #227, 212, |
| | AT THE STAIRWAY ENCLOSURE AND ROOM 221. |
| | |
| | 3.PLAN SHEET M-2.02 - MECHANICAL ROOMS |
| | INDICATE OUTSIDE AIR INTO THE MECH ROOM |
| | BUT NOT TAPPED INTO THE RETURN AIR. |
| | SHOULD THIS MECH ROOM BE A PLENUM, IT |
| | SHALL COMPLY WITH 2001 FBC/M 603.9.NO |
| | COMBUSTIBLES ALLOWED IN THE RETURN AIR |
| | PLENUM. |
| | |
| | 4.PLAN SHEET M-2.03 - FIRE DAMPERS NOT |
| | INDICATED AT THE FOLLOWING LOCATIONS; |
| | ROOMS 308 & 311 AND THE CORRIDOR. |
| | PENETRATIONS ARE ALSO INDICATED AT THE |
| | NORTH, SOUTH AND WEST STARIWAYS. |
| | |
| | 5.PLAN SHEET M-2.04 - FIRE DAMPERS NOT |
| | INDICATED AT THE SIDE WALL GRILLES |
| | TERMINATING AT THE RATED WALL. |
| | |
| | 6.PLAN SHEET C2 INDICATES A/C |
| | CONDENSATE TO THE SEWER WHICH IS |
| | PROHIBITED BY THE CITY CODE SEC. 90-125 |
| | (5). |
| | |
| | 7.PLEASE NOTE THE LIFE SAFETY PLAN AND |
| | ARCHITECTURAL PLANS CONFLICT.THE |
| | ARCHITECTURAL PLANS INDICATE ALL |
| | MECHANICAL ROOM AS HAVING A 1 HR FIRE |
| | RATING & THE LIFE SAFETY PLAN DOES NOT |
| | REFLECT THIS.PER THE 2001 FBC 503 THE |
| | 1HR RATING FOR THE MECHANICAL ROOM IS |
| | NOT REQUIRED.PLEASE CLARIFY AND |
| | CORRELATE THE PLANS.IF THE RATING |
| | SHOULD REMAIN, FIRE DAMEPRS WILL BE |
| | REQUIRED AT THE PENETATRATIONS. |
| | |
| | 8.PROVIDE OUTSIDE AIR CALCULATIONS IN |
| | ACCORDANCE WITH 2001 FBC/M TABLE 403.3. |
| | |
| | 9.PLAN SHEETS A-1.02, A-1.03, A-1.04 |
| | INDICATE "MECH SHAFT", PLEASE PROVIDE |
| | DETAIL OF THE SHAFT AND PENTRATIONS INTO |
| | THE SHAFT. |
| | |
| | 10. PROVIDE INFORMATION AND SUBMITTAL |
| | FOR THE GENERATOR.INDICATE TYPE OF |
| | FUEL (NATURAL GAS, FUEL, DIESEL). |
| | |
| | 11. IDENTIFY EXHAUST DUCT AND |
| | TERMINATION OF EXHAUST. |
| | |
| | 12. SHOW COMPLIANCE WITH THE ENERGY CODE |
| | PER 2001 FBC CHAPTER 13 SECTION 103.0. |
| | |
| | PLEASE NOTE, PLANS ARE TO SIGNED, |
| | SEALED, AND DATED BY THE |
| | ENGINEER/ARCHITECT PER FS471.025 & |
| | 481.221.PLEASE PROVIDE PRINTED NAME |
| | ADDRESS AND PHONE NUMBER OR TITLE BLOCK |
| | AS REQUIRED BY FAC61G15-23.002 & |
| | 61G1-16.004.IF PRACTICING UNDER A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, PROVIDE |
| | CERTIFICATE OF AUTHORIZATION # ON PLANS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |