| Date |
Text |
| 2005-03-10 00:00:00 | 1. PLEASE PROVIDE DOCUMENTATION FROM |
| | NATIONAL, STATE OR THE LOCAL LEVEL |
| | VERIFYING THE HISTORIC BUILDING |
| | DESIGNATION. |
| | |
| | 2. CONSTRUCTION, DEMOLITION, AND |
| | RENOVATION TO COMPLY WITH NFPA 241. |
| | |
| | 3. EXIT STAIRS ARE TO BE KEPT UP |
| | WITH CONSTRUCTION. |
| | |
| | 4. DEBRIS SHALL BE REMOVED FROM THE |
| | SITE DAILY. |
| | |
| | 5. NO CUTTING OR WELDING OPERATIONS |
| | SHALL BE PERFORMED UNLESS APPROVED |
| | BY THE FIRE PREVENTION BUREAU AND |
| | FULL COMPLIANCE WITH NFPA 51B. |
| | |
| | 6. ELECTRONIC SWITCHES, CHAIN AND |
| | LOCKS ARE REQUIRED ON THE BACKFLOW |
| | DEVICE. |
| | |
| | 7. THE FIRE DEPARTMENT CONNECTION |
| | SHALL BE INSTALLED ON THE PROPER |
| | SIDE OF THE BACKFLOW DEVICE. |
| | |
| | 8. A KNOX-BOX WILL BE REQUIRED FOR |
| | THE PROJECT. |
| | |
| | 9. HANDRAILS ARE REQUIRED ON BOTH |
| | SIDES OF NEW STAIRS. |
| | |
| | 10. THE FIRE DEPARTMENT CONNECTION |
| | SHALL BE LOCATED NO FARTHER THAN |
| | 150 FEET FROM A FIRE HYDRANT. |
| | |
| | 11. THE USE OF GASOLINE POWERED |
| | EQUIPMENT INDOORS MUST BE PROVIDED |
| | WITH ADEQUATE VENTILATION TO PREVENT |
| | THE BUILD-UP OF CARBON MONOXIDE. |
| | |
| | 12. THE BUILDING ADDRESS IS REQUIRED |
| | ON THE PROPER ELEVATION. A MINIMUM OF |
| | AT LEAST 6" HIGH NUMBERS ARE REQUIRED. |
| | |
| | 13. MORE DETAILS REQUIRED FOR EMERGENCY |
| | GENERATOR AND FUEL SUPPLY. |
| | |
| | 14. SINCE THE BUILDING WILL BE |
| | CONSIDERED A MIXED OCCUPANCY, THE |
| | MOST STRINGENT OF THE TWO OCCUPANCY |
| | TYPES SHALL GOVERN FOR DESIGN. |
| | |
| | 15. THE LIFE SAFETY PLAN SHALL INDICATE |
| | THAT A COMPLETE AUTOMATIC FIRE |
| | SPRINKLER SYSTEM WILL BE INSTALLED |
| | THROUGHOUT THE BUILDING. |
| | |
| | 16. PLEASE INDICATE TENANT TYPE |
| | ARRANGEMENTS FOR THE BUILDING. WILL |
| | THE TENANT ARRANGEMENTS FOR THE |
| | BUSINESS PORTION BE A SINGLE OR |
| | MULTIPLE TENANT ARRANGEMENT. |
| | |
| | 17. PLEASE EXPLAIN NOTE "EXHIBIT SPACE |
| | ONLY NOT TO BE OCCUPIED". |
| | |
| | 18. A MECHANICAL SHAFT APPEARS TO BE |
| | LOCATED IN SOUTH STAIR 423 ON PAGE |
| | A-0.13. ONLY CERTAIN ITEMS ARE |
| | PERMITTED WITHIN STAIR ENCLOSURES |
| | AND THIS IN NOT ONE OF THEM. |
| | |
| | 19. ELEVATOR WARNING SIGNS ARE REQUIRED. |
| | |
| | 20. EXTERIOR STAIRS SHALL BE SLIP |
| | RESISTANT. |
| | |
| | 21. PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND |
| | CEILINGS. |
| | |
| | 22. ALL SHAFTS THAT ARE LARGE ENOUGH |
| | FOR PERSONS TO FALL INTO MUST BE |
| | MARKED SHAFTWAY WITH 6" HIGH LETTERS. |
| | |
| | 23. ANY STORAGE AREAS LOCATED BENEATH |
| | EXIT STAIRS SHALL BE RATED THE SAME |
| | AS THE STAIRS. |
| | |
| | 24. PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR ALL |
| | HANDRAILS AND GUARDRAILS. |
| | |
| | 25. PLEASE ILLUSTRATE ON THE ELEVATION |
| | DRAWINGS THE LOCATIONS OF ANY OPERABLE |
| | WINDOWS. |
| | |
| | 26. PLEASE EXPLAIN 10" TREADS. |
| | |
| | 27. PLEASE PROVIDE DETAILS ON SEALING |
| | THE EXISTING GLASS TRANSOMES LOCATED |
| | IN THE EXIT CORRIDORS. |
| | |
| | 28. THE WORD "HISTORIC" APPEARS IN |
| | SEVERAL LOCALES ON THE PLANS. PLEASE |
| | PROVIDE MORE DETAILS. |
| | |
| | 29. FIRE SPRINKLER HEADS SHALL NOT |
| | BE IMPEDED BY THE INSTALLATION OF |
| | ANY SOFFITS. |
| | |
| | 30. NO FIRE SPRINKLER DRAWINGS |
| | PROVIDED WITH PLANS. |
| | |
| | 31. THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE MONITORED BY A UL LISTED |
| | CENTRAL STATION APPROVED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 32. THE FIRE ALARM SYSTEM SHALL MONITOR |
| | FIRE PUMP RUN, PUMP FAIL, AND PHASE |
| | REVERSAL. |
| | |
| | 33. SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 34. NO COMBUSTIBLES ALLOWED IN THE |
| | RETURN AIR PLENUM. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |