| Date |
Text |
| 2005-03-10 00:00:00 | ********** UNSAT *********** |
| | |
| | |
| | *** PLAN REVIEW ONLY ******* |
| | PLEASE NOTE, PLANS ARE ONLY IN FOR PLAN |
| | REVIEW AT THIS TIME AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE SEE PLANS ARE NOT |
| | COMPLETE AT THIS TIME FOR FULL REVIEW |
| | FOR CODE COMPLIANCE. |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | PLEASE ALSO SEE AREAS WHERE ELECTRICAL |
| | DEVICES ARE INDICATED IN"LT GRAY" AND |
| | HANDWRITTEN ON PLANS? |
| | |
| | 3)NOTE: PLEASE PROVIDE ALL LIGHT POLE/ |
| | LIGHT FIXTURE WIND LOADING INFORMATION |
| | FOR REVIEW AT THIS TIME. |
| | PLEASE SEE MIN FBC 140 MPH. |
| | IF "SITE LIGHTING" WIND LOAD INFORMATION |
| | AND FIXTURE INFORMATION IS NOT PROVIDED |
| | AT THIS TIME, A SEPARATE PERMIT MAY BE |
| | APPLIED FOR AT A LATER DATE. |
| | |
| | 4)NOTE:PLEASE SEE FAC 61G15-23.002 FOR |
| | MISSING INFORMATION REQUIRED ON TITLE |
| | BLOCK FOR ENG FIRM. PLEASE ALSO SEE FS |
| | 471.023. |
| | PLEASE SEE THIS INFORMATION IS REQUIRED |
| | ON ALL SHEETS AND FOR ALL TRADES |
| | WHEATHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | ** PLEASE SEE WHEN PLANS ARE FINALLY |
| | SUBMITTED FOR PERMIT, PLANS MUST BE |
| | SIGNED, DATED AND SEALED BY ALL |
| | ARCHITECTS AND ENGINEERS RESPONSIBLE FOR |
| | DRAWINGS. |
| | FAC 61G1-16.004,61G15-23.002, FS |
| | 481.221, 471.023 |
| | |
| | 5)NOTE: DUE TO PLANS ONLY IN FOR PLAN |
| | REVIEW AT THIS TIME, IF SUBMITTED AFTER |
| | JULY 1ST, 2005 THE 2005 NEC WILL BE IN |
| | AFFECT. PLEASE SEE NEW REQUIREMENTS FOR |
| | 2005 NEC AND CODES REFERENCE CHANGES. |
| | PLEASE SEE 110.26 FOR CLEARENCE |
| | REQUIREMENTS WHICH WILL CHANGE FOR |
| | EQUIPMENT 1200A'S OR GREATER. |
| | |
| | 6)NOTE: PLEASE SEE 3.03, A "PANEL" IS |
| | SHOWN BUT NO INDICATION OF WHAT PANEL |
| | IS. |
| | PLEASE ALSO SEE NOTE FOR A PANEL LCP-3C, |
| | WITH AN ARROW TO A BLANK AREA? |
| | |
| | 7)NOTE: PLEASE SEE ROOF POWER PLANS IS |
| | SHOWN BLANK? |
| | |
| | 8)NOTE: PLEASE SUBMIT ALL INFORMATION ON |
| | FIRE PUMP/ FIRE PUMP CONTROLLER. |
| | PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| | FOR BOTH. |
| | PLEASE SEE 230.76,230.79 FOR THE |
| | REQUIRED MANUAL MEANS OF DISCONNECT |
| | REQUIRED. PLEASE SPECIFY THIS ON PLANS. |
| | PLEASE PLACE NOTE ONRISER DIAGRAM |
| | THAT THE OVERCURRENT PROTECTIVE |
| | DEVICE(S) SHALL BE SELECTED OR SET TO |
| | CARRY INDEFINITELY THE SUM OF THE |
| | LOCKED-ROTOR CURRENT OF THE FIRE PUMP |
| | MOTOR(S) AND THE PRESSURE MAINTENANCE |
| | PUMP MOTOR(S) AND THE FULL-LOAD CURRENT |
| | OF THE ASSOCIATED FIRE PUMP ACCESSORY |
| | EQUIPMENT WHEN CONNECTED TO THIS POWER |
| | SUPPLY. |
| | |
| | 9)NOTE: PLEASE INDICATE INFORMATION FOR |
| | GENERATOR, GENERATOR SIZE ETC. |
| | PLEASE SUBMIT MANUFACTURE SPEC SHEETS |
| | FOR GEN/ ATS/ GEN SUB-BASE FUEL TANKS |
| | ETC. |
| | PLEASE SEE SIZING OF CONDUCTORS ETC. |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE PLACE PANEL |
| | RATINGS/AMPERAGE ON RISER DIAGRAM FOR |
| | COORDINATION OF FEEDERS INSTALLATION AND |
| | REVIEW. |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE COMPLETE RISER DIAGRAM |
| | WITH ALL NOTATIONS FOR FEEDER SIZES, TO |
| | CORRELATE WITH THE FEEDER SCHEDULE AT |
| | RIGHT. |
| | PLEASE SEE SOME FEEDERS MISSING ON RISER |
| | AND ON FEEDER SCHEDULE. |
| | PLEASE SEE MISSING FEED TO PANEL "LB". |
| | PLEASE SEE MISSING #9 AND #10 FOR |
| | FEEDERS. |
| | PLEASE SEE MISSING OCP FOR FIRE PUMP AT |
| | GENERATOR. |
| | PLEASE SEE MISSING FEEDERS FOR MDAH,MDH, |
| | ETC. |
| | |
| | 12)NOTE: PLEASE SEE NOTE #1 ON E4.10 |
| | ELECTRICAL NOTES MENTIONS, "MAIN CIRCUIT |
| | BREAKERS IN PANEL BOARDS SHALL BE GROUND |
| | FULAT PROTECTED" |
| | PLEASE VERIFY THIS ? PLEASE SEE |
| | 240.13,230.95 ETC WHEN GROUND FAULT |
| | PROTECTION IS REQUIRED. |
| | |
| | 13)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 14)NOTE: PLEASE SHOW OR NOTE ALL TRACK |
| | LIGHTING CALCULATIONS PER 220.12 |
| | |
| | 15)NOTE: PLEASE SEE 250.50 FOR MISSING |
| | COLD WATER PIPE ON GROUNDING ELECTRODE |
| | SYSTEM. |
| | |
| | 16)NOTE: PLEASE SEE 700.16 AND 620.23A |
| | FOR REQUIREMENTS IN ELEC RMS/ ELEV |
| | MACHINE RMS ETC. |
| | |
| | EMERGENCY ILLUMINATION SHALL INCLUDE ALL |
| | REQUIRED MEANS OF EGRESS LIGHTING, |
| | ILLUMINATED EXIT SIGNS, AND ALL OTHER |
| | LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| | REQUIRED ILLUMINATION. |
| | EMERGENCY LIGHTING SYSTEMS SHALL BE |
| | DESIGNED AND INSTALLED SO THAT THE |
| | FAILURE OF ANY INDIVIDUAL LIGHTING |
| | ELEMENT, SUCH AS THE BURNING OUT OF A |
| | LIGHT BULB, CANNOT LEAVE IN TOTAL |
| | DARKNESS ANY SPACE THAT REQUIRES |
| | EMERGENCY ILLUMINATION. |
| | WHERE HIGH-INTENSITY DISCHARGE LIGHTING |
| | SUCH AS HIGH- AND LOW-PRESSURE SODIUM, |
| | MERCURY VAPOR, AND METAL HALIDE IS USED |
| | AS THE SOLE SOURCE OF NORMAL |
| | ILLUMINATION, THE EMERGENCY LIGHTING |
| | SYSTEM SHALL BE REQUIRED TO OPERATE |
| | UNTIL NORMAL ILLUMINATION HAS BEEN |
| | RESTORED. |
| | A SEPARATE BRANCH CIRCUIT SHALL SUPPLY |
| | THE MACHINE ROOM OR CONTROL |
| | ROOM/MACHINERY SPACE OR CONTROL SPACE |
| | LIGHTING AND RECEPTACLE(S). |
| | |
| | PLEASE SEE POSSIBLE NOTES FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SEE SOME OF THESE ITMES LISTED |
| | ABOVE HAVE BEEN REDLINED ON PLANS FOR |
| | AREAS OF NOTES. |
| | |
| | PLEASE SEE NOTE #1. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| 2005-03-08 00:00:00 | ONE ROLL IN ELEC FOR REVIEW. |
| | |
| | PLANS ONLY 50%COMPLETE FORP, M, E |
| | AND FP. |