Plan Review Notes
Plan Review Notes For Permit 05030074
Permit Number 05030074
Review Stop B
Sequence Number 1
Notes
Date Text
2005-03-08 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. WE CANNOT ACCEPT COPIES OF ARCHITECT
 PLANS.
  
 2. NEED FOOTPRINT OF BUILDING WHERE
 WINDOWS ARE TO BE REPLACED. WINDOW
 OPENINGS ARE TO HAVE SIZES & TYPE OF
 WINDOWS. WINDOWS MUST MEET MEANS OF
 EGRESS IN BEDROOMS.
  
 3. NEED 2 COPIES OF FLORIDA PRODUCT
 APPROVALS FOR THE WINDOWS. DADE COUNTY
 PRODUCT APPROVALS ARE UNREADABLE.
  
 4. PER FBC 2001 WHEN MORE THAN 25% OF
 GLASS IS BEING REPLACED THEY HAVE TO
 HAVE HURRICANE PROTECTION. NEED TO KNOW
 HOW MANY WINDOWS ARE BEING REPLACED &
 WHERE THEY ARE IN THE BUILDING.
  
 5. ALWAYS SUBMIT 2 COPIES OF EVERYTHING
 WHEN APPLYING FOR A PERMIT. ONE IS
 RETAINED BY THE CITY AND ONE IS RETURNED
 WITH THE PERMIT.
  
 6. THE APPLICATION STATES THE OWNER
 LIVES AT THE PROPERTY. 2 OTHER PERMITS
 ARE BEING APPLIED FOR WITH THE SAME
 OWNER AND EACH ONE STATES THAT PERSON
 LIVES THERE. WHERE DOES THE OWNER LIVE?
  