Plan Review Notes
Plan Review Notes For Permit 05030042
Permit Number 05030042
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-04 00:00:001} PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND
 CONDUIT SIZE AND TYPE, PANEL RATING AND
 OCP, PANEL SCHEDULE AND COMPUTED LOAD,
 ETC. IF AN ELECTRIC HEATER IS TO BE
 INSTALLEDPLEASE SUBMIT CALCULATIONS
 FOR THE MAINSERVICE.
  
 2} THE SCHEMATIC SUBMITTED FOR REVIEW
 APPEARS TO BE FOR A POOL. PLEASE SUBMIT
 A SCHEMATIC FOR THE SPA.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  