| Plan Review Notes For Permit 05030016 |
| Permit Number |
05030016 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-04-13 00:00:00 | DENIED | | | REFERENCE: FBC-242.2 SWIMMING POOLS | | | FBC-2001 CHAPTER 1 | | | | | | 1) HAND DRAWN CHANGES TO A SIGNED/SEALED | | | SET OF PLANS ARE NOT APPROVED. SECTION | | | 104.2.1.3. NEW SHEETS REQUIRED WITH | | | CHANGES APPROVED BY ENGINEER OF RECORD. | | | 2) POOL ANCHORING SHEET SHALL HAVE THE | | | PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN AFFIXED TO | | | SHEET. SECTION 104.2.1. | | | 3) 3) FBC-2001 424.2.9 WATER SUPPLY, | | | LOCAL ORD. #2853-95, BACKFLOW REQUIRED | | | ON WATER SERVICE. (ADD TO NOTES). | | | 4) FBC-2001 424.2.13.2 JOINTS AND | | | CONNECTIONS, FBC PLUG SEC 605.21 PURPLE | | | PRIMER REQUIRED ON PVC PIPING AND | | | FITTINGS. (ADD TO NOTES). | | | 5) PIPING FOR THE MAIN DRAINS ON THE | | | POOL LAYOUT SHEET DOES NOT REFLECT THE | | | PIPING SHOWN ON THE APPROVED SWIMMING | | | POOL AND WADING POOL MAIN DRAIN | | | ATMOSPHERIC VENT ARRANGEMENT. THE DRAIN | | | SHALL BE DRAINED SIMULTANIOUSLY AND THE | | | VENT LINE SHALL BE SHOWN. SECTIONS | | | 104.2.1 & 424.2.6.6.4. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|