| Plan Review Notes For Permit 05030016 |
| Permit Number |
05030016 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-14 00:00:00 | 3/14/05 DENIED GS | | | | | | 1-FBC 2001 424.2.6.6.2- PROVIDE MODEL | | | NUMBER AND MANUFACTURE INFORMATION FOR | | | VAC.LOCK. | | | 2-424.2.7.1- POOL CIRCULATING PUMPS | | | SHALL BE EQUIPED WITH APPROVED TYPE HAIR | | | AND LINT STRAINER. | | | 3-PUMPS AND EQUIPMENT SHALL BE MOUNTED | | | ON 4" SLAB[ DETAIL ] | | | 4-BACKFLOW REQ. ON WATER SERVICE | | | 5-NO AIR TEST ON PVC PIPE OR FITTINGS | | | 6-FBC 104.2SHOW PIPING FOR THE ENTIRE | | | SYSTEM,PIPE SIZES,VENTS,SUCTION AND | | | DISCHARGE PIPING ETC. |
|