2005-03-04 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE NOTE ON PLANS
 MENTIONS NEW SPEACIALTY LIGHTING,
 HOWEVER NO INFORMATION IS GIVEN FOR
 THIS. PLEASE PROVIDE INFORMATION ON LOAD
 ETC.
  
 2)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS FOR NEW ELECTRICAL AND CORRRELATE
 WITH A PANEL SCHEDULE TO BE SUBMITTED.
  
 3)NOTE: PLEASE SEE 210.8 FOR RECEPTS IN
 BAR AREA ARE TO BE SHOWN AS GFI/ GFI
 PROTECTED.
  
 4)NOTE: PLEASE SEE NOTES FROM FIRE PLAN
 REVIEW WHICH MAY NEED TO VERFIY NEW OR
 EXSITING EM/ EXT LTS.
 NEW OR EXSITING EGRESS LIGHTING IN
 BATHRMS.
 LS 101 5-8
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  