| Plan Review Notes For Permit 05021524 |
| Permit Number |
05021524 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-04 00:00:00 | **** UNSAT **** | | | | | | 1)NOTE: PLEASE SEE NOTE ON PLANS | | | MENTIONS NEW SPEACIALTY LIGHTING, | | | HOWEVER NO INFORMATION IS GIVEN FOR | | | THIS. PLEASE PROVIDE INFORMATION ON LOAD | | | ETC. | | | | | | 2)NOTE: PLEASE PROVIDE CIRCUITING ON | | | PLANS FOR NEW ELECTRICAL AND CORRRELATE | | | WITH A PANEL SCHEDULE TO BE SUBMITTED. | | | | | | 3)NOTE: PLEASE SEE 210.8 FOR RECEPTS IN | | | BAR AREA ARE TO BE SHOWN AS GFI/ GFI | | | PROTECTED. | | | | | | 4)NOTE: PLEASE SEE NOTES FROM FIRE PLAN | | | REVIEW WHICH MAY NEED TO VERFIY NEW OR | | | EXSITING EM/ EXT LTS. | | | NEW OR EXSITING EGRESS LIGHTING IN | | | BATHRMS. | | | LS 101 5-8 | | | | | | PLEASE SEE OTHER POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|