Plan Review Notes
Plan Review Notes For Permit 05021387
Permit Number 05021387
Review Stop E
Sequence Number 4
Notes
Date Text
2006-08-23 00:00:00*** 4TH REVIEW ***
  
 THIS PERMIT IS STILL UNDER THE 2001 FBC.
  
 1) NOTE: PLEASE CORRELATE ALL AIC
 RATINGS ON PLANS. PLEASE VERIFY THE
 AVAILABLE FAULT CURRENT AS THE NEW
 METER/COMBO IS BEING SHOWN AS 42K WHICH
 IS MENTIONED AS 80 FT AWAY FROM THE FPL
 TRANSFORMER.
 PLEASE KNOW, THE FURTHER AWAY, THE LESS
 THE AVAILABLE FAULT CURRENT IS. PLEASE
 SEE PLANS INDICATE THE PANEL UPSTAIRS AS
 22K NAD RISER SHOWS THIS PANEL AS 10K.
 PLEASE SEE A/C DISCONNECT IS BEING SHOWN
 AS 10K RATED. PLEASE KNOW, THE RATING OF
 THE A/C DISCONNECT IS NOT NEEDED.
 110.9,
 FBC 104.2.1
  
 2) NOTE: PLEASE SEE 210.21B3, PLEASE SEE
 A RANGE/STOVE RECEPT IS 50A RATED,
 PLEASE SEE PANEL SCHEDULE IS SHOWING A
 60A BRKR. PLEASE SEE CODE ABOVE, NO MORE
 THAN 50A OCP IS PERMITTED.
  
 3) NOTE: PLEASE KNOW, IT IS UNDERSTOOD
 FROM THIS OFFICE THE DOWNSTAIRS IS
 HAVING TO BE BROUGHT UP TO CODE AND MUST
 BE DONE AT THIS TIME. (EVEN IF FOR SHELL
 OF FUTURE OFFICE)
 PLEASE SHOW THE LOCATION OF THE NEW
 PANEL AND SHOW MIN LTS REQUIRED FOR
 EGRESS AND EXITING.
 PLEASE KNOW, WE ARE UNABLE TO VERIFY THE
 MIN CLEARENCES FOR THE PANEL PER 110.26
 AND LOCATION FOR PANEL PER 240.24.
 PLEASE SEE NFPA-101 2003 FOR MIN LTS FOR
 EXT AND EM LTS. 7.8, 7.9
  
 4) NOTE: PLEASE SEE LOAD CALCULATIONS
 ARE SHOWING LOAD FOR WHAT SEEMS TO BE
 DEDICATED RECEPTS OF SOME SORT YET THIS
 COULD NOT BE FOUND ON PANEL SCHEDULE.
 (3KW)? PLEASE SEE 500VA ALSO SHOWN FOR
 SD'S?
 PLEASE SEE ALL GEN LTS AND RECEPTS FOR
 UPPER SPACE SHALL BE INCLUDED IN THE MIN
 3VA PER SQ FT.
 220.31
  
 5) NOTE: PLEASE SEE THE PLANS SHALL
 INDICATE ALL THE RELEVANT CODES AT A
 MIN.
 2001 FBC, 2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101
  
 6) NOTE: PLEASE SEE A RESPONSE NOTE
 MENTIONS A CONFLICT IN ELECTRICAL REVIEW
 AND FIRE REVIEW FOR REQUIRMENT OF THE
 SD'S OUTSIDE SLEEPING ROOMS/ AND
 KITCHENS.
 PLEASE SEE NFPA-72 11.8.3, 11.5.1.1,
 SD'S ARE REQUIRED OUTSIDE ALL SLEEPING
 ROOMS AND IF WITHIN 20' OF COOKING
 APPLIANCES, THEN THE SD'S MUST BE
 RE-SETTING TYPE/PHOTO-ELECTRIC EYE.
  
 7) NOTE: PLEASE BE SURE THE ENERGY
 CALCULATIONS SUBMITTED CONTAIN AN
 ORIGINAL SIGNATURE, DATE AND SEAL FROM
 THE DESIGN PROFESSIONAL.
 FS471.025
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  