| Date |
Text |
| 2006-08-23 00:00:00 | *** 4TH REVIEW *** |
| | |
| | THIS PERMIT IS STILL UNDER THE 2001 FBC. |
| | |
| | 1) NOTE: PLEASE CORRELATE ALL AIC |
| | RATINGS ON PLANS. PLEASE VERIFY THE |
| | AVAILABLE FAULT CURRENT AS THE NEW |
| | METER/COMBO IS BEING SHOWN AS 42K WHICH |
| | IS MENTIONED AS 80 FT AWAY FROM THE FPL |
| | TRANSFORMER. |
| | PLEASE KNOW, THE FURTHER AWAY, THE LESS |
| | THE AVAILABLE FAULT CURRENT IS. PLEASE |
| | SEE PLANS INDICATE THE PANEL UPSTAIRS AS |
| | 22K NAD RISER SHOWS THIS PANEL AS 10K. |
| | PLEASE SEE A/C DISCONNECT IS BEING SHOWN |
| | AS 10K RATED. PLEASE KNOW, THE RATING OF |
| | THE A/C DISCONNECT IS NOT NEEDED. |
| | 110.9, |
| | FBC 104.2.1 |
| | |
| | 2) NOTE: PLEASE SEE 210.21B3, PLEASE SEE |
| | A RANGE/STOVE RECEPT IS 50A RATED, |
| | PLEASE SEE PANEL SCHEDULE IS SHOWING A |
| | 60A BRKR. PLEASE SEE CODE ABOVE, NO MORE |
| | THAN 50A OCP IS PERMITTED. |
| | |
| | 3) NOTE: PLEASE KNOW, IT IS UNDERSTOOD |
| | FROM THIS OFFICE THE DOWNSTAIRS IS |
| | HAVING TO BE BROUGHT UP TO CODE AND MUST |
| | BE DONE AT THIS TIME. (EVEN IF FOR SHELL |
| | OF FUTURE OFFICE) |
| | PLEASE SHOW THE LOCATION OF THE NEW |
| | PANEL AND SHOW MIN LTS REQUIRED FOR |
| | EGRESS AND EXITING. |
| | PLEASE KNOW, WE ARE UNABLE TO VERIFY THE |
| | MIN CLEARENCES FOR THE PANEL PER 110.26 |
| | AND LOCATION FOR PANEL PER 240.24. |
| | PLEASE SEE NFPA-101 2003 FOR MIN LTS FOR |
| | EXT AND EM LTS. 7.8, 7.9 |
| | |
| | 4) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | ARE SHOWING LOAD FOR WHAT SEEMS TO BE |
| | DEDICATED RECEPTS OF SOME SORT YET THIS |
| | COULD NOT BE FOUND ON PANEL SCHEDULE. |
| | (3KW)? PLEASE SEE 500VA ALSO SHOWN FOR |
| | SD'S? |
| | PLEASE SEE ALL GEN LTS AND RECEPTS FOR |
| | UPPER SPACE SHALL BE INCLUDED IN THE MIN |
| | 3VA PER SQ FT. |
| | 220.31 |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS SHALL |
| | INDICATE ALL THE RELEVANT CODES AT A |
| | MIN. |
| | 2001 FBC, 2002 NFPA-70, 2002 NFPA-72, |
| | 2003 NFPA-101 |
| | |
| | 6) NOTE: PLEASE SEE A RESPONSE NOTE |
| | MENTIONS A CONFLICT IN ELECTRICAL REVIEW |
| | AND FIRE REVIEW FOR REQUIRMENT OF THE |
| | SD'S OUTSIDE SLEEPING ROOMS/ AND |
| | KITCHENS. |
| | PLEASE SEE NFPA-72 11.8.3, 11.5.1.1, |
| | SD'S ARE REQUIRED OUTSIDE ALL SLEEPING |
| | ROOMS AND IF WITHIN 20' OF COOKING |
| | APPLIANCES, THEN THE SD'S MUST BE |
| | RE-SETTING TYPE/PHOTO-ELECTRIC EYE. |
| | |
| | 7) NOTE: PLEASE BE SURE THE ENERGY |
| | CALCULATIONS SUBMITTED CONTAIN AN |
| | ORIGINAL SIGNATURE, DATE AND SEAL FROM |
| | THE DESIGN PROFESSIONAL. |
| | FS471.025 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |