| Date |
Text |
| 2006-09-27 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | THE FOLLOWING COMMENTS ARE FROM THE |
| | PREVIOUS LIST, NOT PROPERLY ADDRESSED. |
| | NUMBERING HAS REMAINED THE SAME FOR |
| | CONSISTENCY.NOTE THAT SOME OF THE NEW |
| | COMMENTS WERE PREVIOUSLY ADDRESSED BUT |
| | ARE NOT ON THIS SET OF PLANS; OLD SHEETS |
| | NOT SUBMITTED: |
| | |
| | 1.)FROM PREVIOUS LISTS: |
| | |
| | THE EXTERIOR STAIR IS TO COMPLY |
| | WITH FBC1006.2.4.PROVIDE ELEVATIONS |
| | AND INDICATE, TO SCALE, ALL OPENINGS |
| | WHICH REQUIRE FIRE RESISTANCE.SHOW ONE |
| | HOUR RATING REQUIRED ON THE PLAN. |
| | |
| | ONE HOUR RATING REQUIREMENT NOT SHOWN. |
| | YOUR RESPONSE LETTER THAT THE WALL IS |
| | BLOCK AND IS 1 HOUR IS ACKNOWLEDGED BUT |
| | IS TO BE SHOWN ON THE PLAN (1 HOUR |
| | REQUIRED).THE OPENINGS ON THE SECOND |
| | FLOOR WHICH ARE REQUIRED TO BE PROTECTED |
| | ARE NOTED BUT NOTHING IS SHOWN FOR THE |
| | FIRST FLOOR.PROVIDE ELEVATIONS AS |
| | REQUESTED IN EACH PLAN REVIEW AND NOTE |
| | THE 1 HOUR REQUIREMENT ON THE PLAN. |
| | |
| | 2.)ADDRESSED |
| | |
| | 3.)DOCUMENTS PREPARED BY AN ENGINEER |
| | AND SUBMITTED FOR PUBLIC RECORD ARE TO |
| | BE SIGNED, SEALED, DATED ORIGINALS |
| | FAC61G15-23.002 (ENERGY CALCS). |
| | |
| | SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALCS, FBC*103.1. |
| | |
| | 4.)SEE PREVIOUS LISTS IN REGARDS TO |
| | HURRICANE SHUTTERS.THERE IS A |
| | STATEMENT ON THE PLAN THAT ALL SHUTTERS |
| | WILL BE ACCORDION, BUT STORM PANEL |
| | PRODUCT APPROVALS WERE SUBMITTED AND A |
| | STORAGE AREA SHOWN FOR THE SHUTTERS. |
| | SEE THE ATTACHED WIND-BORNE DEBRIS |
| | IMPACT PROTECTION STANDARD, ITEMS 13 AND |
| | 14.SUBMIT AN INSTALLATION PLAN AS |
| | REQUIRED.THE PLAN MAY BE SUBMITTED |
| | SEPARATELY FROM THE PERMIT APPLICATION. |
| | A PRELIMINARY REVIEW CAN BE DONE BY |
| | EMAIL; SUBMIT TO [email protected] |
| | PRELIMINARY REVIEW, THE PLAN IS |
| | FORWARDED TO THE BUILDING OFFICIAL.THE |
| | PLAN MUST BE APPROVED PRIOR TO PERMIT |
| | ISSUANCE.CONTINUED FAILURE TO ADDRESS |
| | THIS COMMENT WILL RESULT IN ADDITIONAL |
| | PERMIT DELAYS. |
| | |
| | 5.)COMPLETE THE ATTACHED INSTALLATION |
| | SCHEDULE (SHUTTERS), OR PROVIDE ALL |
| | REQUIRED INFORMATION IN A SIMILAR |
| | FORMAT. |
| | |
| | 6.)PRODUCT APPROVALS FOR JELD-WEN |
| | DOORS WERE SUBMITTED.THERE ARE THREE |
| | DIFFERENT PRODUCT APPROVALS IN THE |
| | BROCHURE.SUBMIT ONLY THE DOOR YOU WILL |
| | INSTALL. |
| | |
| | 7.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED IN ADDITION TO NOAS |
| | SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | THIS WAS ADDRESSED WITH FBC2001 PRODUCT |
| | APPROVALS.NOTE THAT A NEW APPLICATION |
| | WILL BE UNDER FBC2004, PROVIDE CURRENT |
| | (2004) PRODUCT APPROVALS. |
| | |
| | FBC2004 REQUIRES THAT PRODUCT APPROVALS |
| | BE REVIEWED BY DESIGNER OF RECORD, |
| | FBC*106.3.3. |
| | |
| | 8.)SEE PREVIOUS LIST, ITEM #6. |
| | PROVIDE FIRE RATING INFORMATION FOR THE |
| | PRODUCT YOU ARE INSTALLING.THE PRODUCT |
| | APPROVALS FOR THE DOORS DO NOT INDICATE |
| | THAT THEY HAVE A FIRE RATING. |
| | |
| | 9.)SEE PREVIOUS LIST, ITEM #6.THE |
| | ENTRY DOORS ARE TO BE APPROVED BY |
| | HISTORIC PRIOR TO RESUBMITTAL AS PER |
| | THEIR LETTER DATED 11/20/03, WHICH IS NO |
| | LONGER IN THE PACKAGE. |
| | |
| | HAVE HISTORIC STAMP THE PRODUCT |
| | APPROVAL.THEY HAVE STATED THAT THEY |
| | DID NOT DO A REVIEW, ONLY THAT THEY |
| | STAMPED THE RESUBMITTAL SHEET. |
| | |
| | 10.)YOU HAVE DONE A CHANGE TO THE |
| | EXTERIOR OF THE BUILDING (ADDED |
| | ACCORDION SHUTTERS).THIS REQUIRES |
| | APPROVAL FROM HISTORIC PRESERVATION |
| | DEPARTMENT. |
| | |
| | 11.)PRODUCT APPROVAL FOR TRACO SINGLE |
| | HUNG EGRESS WINDOW WAS SUBMITTED.THIS |
| | IS ACCEPTABLE FOR THE WINDOWS WHICH ARE |
| | NOT REQUIRED TO BE FIRE RATED; HOWEVER, |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72.PLEASE PROVIDE. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 12.)PROVIDE PRODUCT APPROVALS AND FIRE |
| | RATING |
| | INFORMATION FOR THE FIRE RATED WINDOWS. |
| | |
| | 13.-17.)ADDRESSED. |
| | |
| | 18.)REVISE THE PERMIT APPLICATION |
| | DESCRIPTION OF WORK.THIS IS NOT ONLY |
| | AN INTERIOR REMODEL. |
| | |
| | 19.)SEE ELECTRIC REVIEW #2 AND THE |
| | ATTACHED FS553.80(2)(B).A 4X PLAN |
| | REVIEW FEE HAS BEEN CHARGED AS REQUIRED |
| | BY FLORIDA STATUTE.A RESUB FEE WILL |
| | NOT BE CHARGED.A BILL IS ATTACHED AND |
| | MUST BE PAID PRIOR TO RESUBMITTAL.THIS |
| | AMOUNT WILL CHANGE WHEN CORRECT |
| | VALUATION IS DETERMINED. |
| | |
| | NEW COMMENTS: |
| | |
| | 20.)OCCUPANCY SEPARATION REQUIRED. |
| | SPECIFY THE HORIZONTAL SEPARATION |
| | BETWEEN THE BUSINESS AND RESIDENTIAL |
| | OCCUPANCIES, FBC TABLE 704.1. |
| | |
| | 21.)THIS PERMIT APPLICATION HAS |
| | EXPIRED, FBC*104.1.6, OVER SIX MONTHS |
| | WITH NO ACTIVITY (12/22/05 TO 8/7/06). |
| | SUBMIT A NEW PERMIT APPLICATION WITH NEW |
| | PLANS.NOTE THAT GOVERNING CODE HAS |
| | CHANGED EFFECTIVE OCTOBER 1, 2006 |
| | (FBC2004). |
| | |
| | 22.)THE ROOF AND ROOF FRAMING PERMIT |
| | 04100264, 04050602 ARE ALSO EXPIRED. |
| | APPLY FOR NEW PERMITS.A LICENSED |
| | ROOFING CONTRACTOR WILL BE REQUIRED FOR |
| | THE ROOF PERMIT; A CBC CANNOT DO ROOFING |
| | WORK ON A MODIFIED SYSTEM (NAIL-ON |
| | SYSTEMS ONLY).INCLUDE ALL WORK |
| | REQUIRED TO COMPLY WITH THE CBAA ORDER |
| | WHEN RESUBMITTING (2ND FLOOR FRAMING, |
| | ROOF FRAMING, ROOF). |
| | |
| | 23.)DECLARE AN OCCUPANCY |
| | SUBCLASSIFICATION, FBC311. |
| | |
| | 24.)THE HANDRAIL IS TO BE 34 TO 38IN, |
| | FBC1007.5 UNLESS A PART OF THE |
| | GUARDRAIL. |
| | |
| | 25.)HANDRAIL EXTENSIONS REQUIRED AT |
| | TOP AND BOTTOM OF THE STAIR, PROVIDE |
| | DETAILS AND SHOW ON THE FLOOR PLAN, |
| | FBC1007.5.5. |
| | |
| | 26.)HANDRAILS AND GUARDRAILS TO COMPLY |
| | WITH FBC1608.2.1.1 AND FBC1608.2.2 |
| | RESPECTIVELY.PLEASE STATE DESIGN |
| | CRITERIA ON THE PLAN. |