Plan Review Notes
Plan Review Notes For Permit 05021387
Permit Number 05021387
Review Stop B
Sequence Number 4
Notes
Date Text
2006-09-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 THE FOLLOWING COMMENTS ARE FROM THE
 PREVIOUS LIST, NOT PROPERLY ADDRESSED.
 NUMBERING HAS REMAINED THE SAME FOR
 CONSISTENCY.NOTE THAT SOME OF THE NEW
 COMMENTS WERE PREVIOUSLY ADDRESSED BUT
 ARE NOT ON THIS SET OF PLANS; OLD SHEETS
 NOT SUBMITTED:
  
 1.)FROM PREVIOUS LISTS:
  
 THE EXTERIOR STAIR IS TO COMPLY
 WITH FBC1006.2.4.PROVIDE ELEVATIONS
 AND INDICATE, TO SCALE, ALL OPENINGS
 WHICH REQUIRE FIRE RESISTANCE.SHOW ONE
 HOUR RATING REQUIRED ON THE PLAN.
  
 ONE HOUR RATING REQUIREMENT NOT SHOWN.
 YOUR RESPONSE LETTER THAT THE WALL IS
 BLOCK AND IS 1 HOUR IS ACKNOWLEDGED BUT
 IS TO BE SHOWN ON THE PLAN (1 HOUR
 REQUIRED).THE OPENINGS ON THE SECOND
 FLOOR WHICH ARE REQUIRED TO BE PROTECTED
 ARE NOTED BUT NOTHING IS SHOWN FOR THE
 FIRST FLOOR.PROVIDE ELEVATIONS AS
 REQUESTED IN EACH PLAN REVIEW AND NOTE
 THE 1 HOUR REQUIREMENT ON THE PLAN.
  
 2.)ADDRESSED
  
 3.)DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G15-23.002 (ENERGY CALCS).
  
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALCS, FBC*103.1.
  
 4.)SEE PREVIOUS LISTS IN REGARDS TO
 HURRICANE SHUTTERS.THERE IS A
 STATEMENT ON THE PLAN THAT ALL SHUTTERS
 WILL BE ACCORDION, BUT STORM PANEL
 PRODUCT APPROVALS WERE SUBMITTED AND A
 STORAGE AREA SHOWN FOR THE SHUTTERS.
 SEE THE ATTACHED WIND-BORNE DEBRIS
 IMPACT PROTECTION STANDARD, ITEMS 13 AND
 14.SUBMIT AN INSTALLATION PLAN AS
 REQUIRED.THE PLAN MAY BE SUBMITTED
 SEPARATELY FROM THE PERMIT APPLICATION.
 A PRELIMINARY REVIEW CAN BE DONE BY
 EMAIL; SUBMIT TO [email protected]
 PRELIMINARY REVIEW, THE PLAN IS
 FORWARDED TO THE BUILDING OFFICIAL.THE
 PLAN MUST BE APPROVED PRIOR TO PERMIT
 ISSUANCE.CONTINUED FAILURE TO ADDRESS
 THIS COMMENT WILL RESULT IN ADDITIONAL
 PERMIT DELAYS.
  
 5.)COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE (SHUTTERS), OR PROVIDE ALL
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.
  
 6.)PRODUCT APPROVALS FOR JELD-WEN
 DOORS WERE SUBMITTED.THERE ARE THREE
 DIFFERENT PRODUCT APPROVALS IN THE
 BROCHURE.SUBMIT ONLY THE DOOR YOU WILL
 INSTALL.
  
 7.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED IN ADDITION TO NOAS
 SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 THIS WAS ADDRESSED WITH FBC2001 PRODUCT
 APPROVALS.NOTE THAT A NEW APPLICATION
 WILL BE UNDER FBC2004, PROVIDE CURRENT
 (2004) PRODUCT APPROVALS.
  
 FBC2004 REQUIRES THAT PRODUCT APPROVALS
 BE REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 8.)SEE PREVIOUS LIST, ITEM #6.
 PROVIDE FIRE RATING INFORMATION FOR THE
 PRODUCT YOU ARE INSTALLING.THE PRODUCT
 APPROVALS FOR THE DOORS DO NOT INDICATE
 THAT THEY HAVE A FIRE RATING.
  
 9.)SEE PREVIOUS LIST, ITEM #6.THE
 ENTRY DOORS ARE TO BE APPROVED BY
 HISTORIC PRIOR TO RESUBMITTAL AS PER
 THEIR LETTER DATED 11/20/03, WHICH IS NO
 LONGER IN THE PACKAGE.
  
 HAVE HISTORIC STAMP THE PRODUCT
 APPROVAL.THEY HAVE STATED THAT THEY
 DID NOT DO A REVIEW, ONLY THAT THEY
 STAMPED THE RESUBMITTAL SHEET.
  
 10.)YOU HAVE DONE A CHANGE TO THE
 EXTERIOR OF THE BUILDING (ADDED
 ACCORDION SHUTTERS).THIS REQUIRES
 APPROVAL FROM HISTORIC PRESERVATION
 DEPARTMENT.
  
 11.)PRODUCT APPROVAL FOR TRACO SINGLE
 HUNG EGRESS WINDOW WAS SUBMITTED.THIS
 IS ACCEPTABLE FOR THE WINDOWS WHICH ARE
 NOT REQUIRED TO BE FIRE RATED; HOWEVER,
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72.PLEASE PROVIDE.
 WWW.FLORIDABUILDING.ORG
  
 12.)PROVIDE PRODUCT APPROVALS AND FIRE
 RATING
 INFORMATION FOR THE FIRE RATED WINDOWS.
  
 13.-17.)ADDRESSED.
  
 18.)REVISE THE PERMIT APPLICATION
 DESCRIPTION OF WORK.THIS IS NOT ONLY
 AN INTERIOR REMODEL.
  
 19.)SEE ELECTRIC REVIEW #2 AND THE
 ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE HAS BEEN CHARGED AS REQUIRED
 BY FLORIDA STATUTE.A RESUB FEE WILL
 NOT BE CHARGED.A BILL IS ATTACHED AND
 MUST BE PAID PRIOR TO RESUBMITTAL.THIS
 AMOUNT WILL CHANGE WHEN CORRECT
 VALUATION IS DETERMINED.
  
 NEW COMMENTS:
  
 20.)OCCUPANCY SEPARATION REQUIRED.
 SPECIFY THE HORIZONTAL SEPARATION
 BETWEEN THE BUSINESS AND RESIDENTIAL
 OCCUPANCIES, FBC TABLE 704.1.
  
 21.)THIS PERMIT APPLICATION HAS
 EXPIRED, FBC*104.1.6, OVER SIX MONTHS
 WITH NO ACTIVITY (12/22/05 TO 8/7/06).
 SUBMIT A NEW PERMIT APPLICATION WITH NEW
 PLANS.NOTE THAT GOVERNING CODE HAS
 CHANGED EFFECTIVE OCTOBER 1, 2006
 (FBC2004).
  
 22.)THE ROOF AND ROOF FRAMING PERMIT
 04100264, 04050602 ARE ALSO EXPIRED.
 APPLY FOR NEW PERMITS.A LICENSED
 ROOFING CONTRACTOR WILL BE REQUIRED FOR
 THE ROOF PERMIT; A CBC CANNOT DO ROOFING
 WORK ON A MODIFIED SYSTEM (NAIL-ON
 SYSTEMS ONLY).INCLUDE ALL WORK
 REQUIRED TO COMPLY WITH THE CBAA ORDER
 WHEN RESUBMITTING (2ND FLOOR FRAMING,
 ROOF FRAMING, ROOF).
  
 23.)DECLARE AN OCCUPANCY
 SUBCLASSIFICATION, FBC311.
  
 24.)THE HANDRAIL IS TO BE 34 TO 38IN,
 FBC1007.5 UNLESS A PART OF THE
 GUARDRAIL.
  
 25.)HANDRAIL EXTENSIONS REQUIRED AT
 TOP AND BOTTOM OF THE STAIR, PROVIDE
 DETAILS AND SHOW ON THE FLOOR PLAN,
 FBC1007.5.5.
  
 26.)HANDRAILS AND GUARDRAILS TO COMPLY
 WITH FBC1608.2.1.1 AND FBC1608.2.2
 RESPECTIVELY.PLEASE STATE DESIGN
 CRITERIA ON THE PLAN.