Plan Review Notes
Plan Review Notes For Permit 05021387
Permit Number 05021387
Review Stop E
Sequence Number 3
Notes
Date Text
2005-12-21 00:00:00*** UNSAT ***
  
 PLEASE SEE MANY NEW COMMENTS DUE TO
 CHANGES MADE TO PLANS.
 PLEASE ALSO SEE COMMENT FROM OTHER
 REVIEWS NOT ADDRESSED.
  
  
 1)NOTE: PLEASE SEE PLANS HAVE NOW
 DELETED TWO OF THE REQUIRED SD'S ON
 PLANS?
 NFPA-72 11.5.1.1
  
 2)NOTE: PLEASE ALSO PREVIOUS PLANS HAD
 MADE CORRECTIONS FOR SD'S TO BE ON AN
 ARC FAULT PROTECTED CIRCUIT AS REQUIRED
 PER 2002 210.12 AND NOTED ON PREVIOUS
 REVIEWS, HOWEVER PLEASE SEE THIS CIRCUIT
 AHS NOW REMOVED THE ARC FAULT
 PROTECTION.???
  
 3)NOTE: PLEASE SEE PLANS DO NOT SHOW THE
 NEW SERVICE LOCATION ON PLANS. PLEASE
 SEE PLANS ONLY INDICATE THE NEW METER.
 215.5
  
 4)NOTE: PLEASE NOW SEE THE NEW SERVICE
 RISER HAS COMPLETELY CHANGED WHICH IS
 INTRODUCING MANY NEW COMMENTS.
  
 PLEASE SEE CONDUCTORS ON RISER AND FOR
 FEEDERS TO PANELS ARE INDICATING SERVICE
 BEING A 3-PHASE SERVICE.PLEASE ADJUST
  
 PLEASE SEE RISER SHOWS A 200A FEED TO A
 200A PANEL , HOWEVER , PLEASE SEE NO
 PANEL SCHEDULE SUBMITTED TO CORRELATE
 WITH THIS. THE ONLY PANEL SCHEDULE SHOWN
 IS A 150A PANEL FOR UNIT UPSTAIRS.
  
 PLEASE SEE GROUNDING ELECTRODE CONDUCTOR
 IS NOW REQUIRED TO BE INCREADED PER
 250.66 AND SIZING OF SEC'S.
  
 5)NOTE: PLEASE SEE TWO CIRCUITS GOING TO
 THE SAME DEVICE IN BEDRMS. (SWITCHED
 RECEPT) PLEASE SEE THIS WOULD REQUIRE
 THE USE OF A TWO POLE BREAKER IN PANEL,
 HOWEVER PLEASE SEE THERE ARE THREE
 CIRCUITS SHARED IN THIS SCENERIO WHICH
 WOULD BE ABLE TO BE DONE.
  
 6)NOTE: PLEASE SEE NOW LOAD CALCUALTIONS
 SUBMITTED FOR FIRST FLOOR WHICH DO NO
 CORRELATE WITH THE NEC AND OFFICE OR
 MERCHANTILE OCCUPANCY AS INIDCATED ON
 THE PLANS.
 PLEASE SEE 220 OF THE NEC FOR CORRECTED
 LOAD CALCS.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
 ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%.
  
 ** PLEASE SEE ONE SET OF NEW PLANS AND
 OLD HAVE BEEN RETAINED FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]