2005-12-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE PREVIOUS LIST, ITEM #5.NOTE
 THE 1 HOUR FIRE RATING REQUIREMENT FOR
 THE WALL AT THE EXTERIOR STAIR.
  
 2.)SEE PREVIOUS LIST, ITEM #7,
 FBC1006.2.4.NOTE THE FOLLOWING:
  
 A. THE DOOR IS TO HAVE A CLOSER; "FIXED
 OR SELF-CLOSING OPENING PROTECTIVES."
  
 B. THE PLANS SPECIFY 2 HOUR FIRE RATED
 ENTRY DOORS.THE MINIMUM CODE
 REQUIREMENT IS A 45 MINUTE ASSEMBLY.IT
 IS ACCEPTABLE TO EXCEED CODE; HOWEVER, I
 AM BRINGING THIS TO YOUR ATTENTION.
  
 C. THE WINDOWS SPECIFIED ON THE PLAN ARE
 SINGLE HUNG.THIS DOES NOT COMPLY WITH
 THE REQUIREMENT "SHALL BE EQUIPPED WITH
 FIXED 3/4 HOUR ASSEMBLIES."
  
 D. SPECIFY FIRE RATING REQUIREMENT FOR
 THE WINDOWS.
  
 3.)THE ENERGY CALCS WHICH WERE
 PREVIOUSLY SUBMITTED ARE NO LONGER IN
 THE PACKAGE.
  
 4.)SEE PREVIOUS LIST, ITEM #10.
 POLICY IN REGARDS TO MISSILE IMPACT
 PROTECTION IS ATTACHED.THE PLAN NOW
 SPECIFIES ACCORDION SHUTTERS, BUT
 PRODUCT APPROVALS FOR GALVANIZED STEEL
 SHUTTERS WERE SUBMITTED.REMOVABLE
 SHUTTERS NOT ALLOWED FOR THE SECOND
 FLOOR, AND REMOVABLE SHUTTERS MUST BE
 APPROVED BY THE BUILDING OFFICIAL FOR
 THE FIRST FLOOR.ADDRESS.
  
 5.)COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE (SHUTTERS), OR PROVIDE ALL
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.
  
 6.)PRODUCT APPROVALS FOR JELD-WEN
 DOORS WERE SUBMITTED.THERE ARE THREE
 DIFFERENT PRODUCT APPROVALS IN THE
 BROCHURE.SUBMIT ONLY THE DOOR YOU WILL
 INSTALL.
  
 7.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED IN ADDITION TO NOAS
 SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 8.)SEE PREVIOUS LIST, ITEM #6.
 PROVIDE FIRE RATING INFORMATION FOR THE
 PRODUCT YOU ARE INSTALLING.THE PRODUCT
 APPROVALS FOR THE DOORS DO NOT INDICATE
 THAT THEY HAVE A FIRE RATING.
  
 9.)SEE PREVIOUS LIST, ITEM #6.THE
 ENTRY DOORS ARE TO BE APPROVED BY
 HISTORIC PRIOR TO RESUBMITTAL AS PER
 THEIR LETTER DATED 11/20/03, WHICH IS NO
 LONGER IN THE PACKAGE.
  
 10.)YOU HAVE DONE A CHANGE TO THE
 EXTERIOR OF THE BUILDING (ADDED
 ACCORDION SHUTTERS).THIS REQUIRES
 APPROVAL FROM HISTORIC PRESERVATION
 DEPARTMENT.
  
 11.)PRODUCT APPROVAL FOR TRACO SINGLE
 HUNG EGRESS WINDOW WAS SUBMITTED.THIS
 IS ACCEPTABLE FOR THE WINDOWS WHICH ARE
 NOT REQUIRED TO BE FIRE RATED; HOWEVER,
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72.PLEASE PROVIDE.
 WWW.FLORIDABUILDING.ORG
  
 12.)PRODUCT APPROVALS AND FIRE RATING
 INFORMATION FOR THE FIRE RATED WINDOWS.
  
 13.)SEE FBC905.2.2 IN REGARDS TO SMOKE
 DETECTOR REQUIREMENTS.
  
 14.)SEE PREVIOUS LIST, ITEM #20, IN
 REGARDS TO VALUATION.
  
 15.)SEE PREVIOUS TWO LISTS, ITEM #21,
 IN REGARDS TO ROOF DRAINS AND OVERFLOW
 DRAINS.SCUPPERS ARE SHOWN BUT NO
 INFORMATION PROVIDED IN REGARDS TO
 PRIMARY AND SECONDARY DRAINAGE SYSTEM.
 SEE FBC1503.4.
  
 16.)PROVIDE A DETAIL FOR THE PRIMARY
 AND SECONDARY SCUPPERS, FBC1503.4,
 FBC1503.4.2.
  
 17.)PROVIDE THE PARAPET WALL HEIGHT AS
 THIS INFORMATION IS REQUIRED TO
 DETERMINE DRAINAGE REQUIREMENTS.
  
 18.)REVISE THE PERMIT APPLICATION
 DESCRIPTION OF WORK.THIS IS NOT ONLY
 AN INTERIOR REMODEL.
  
 19.)SEE ELECTRIC REVIEW #2 AND THE
 ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE HAS BEEN CHARGED AS REQUIRED
 BY FLORIDA STATUTE.A RESUB FEE WILL
 NOT BE CHARGED.A BILL IS ATTACHED AND
 MUST BE PAID PRIOR TO RESUBMITTAL.THIS
 AMOUNT WILL CHANGE WHEN CORRECT
 VALUATION IS DETERMINED.
  