| 2005-12-22 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)SEE PREVIOUS LIST, ITEM #5.NOTE |
| | THE 1 HOUR FIRE RATING REQUIREMENT FOR |
| | THE WALL AT THE EXTERIOR STAIR. |
| | |
| | 2.)SEE PREVIOUS LIST, ITEM #7, |
| | FBC1006.2.4.NOTE THE FOLLOWING: |
| | |
| | A. THE DOOR IS TO HAVE A CLOSER; "FIXED |
| | OR SELF-CLOSING OPENING PROTECTIVES." |
| | |
| | B. THE PLANS SPECIFY 2 HOUR FIRE RATED |
| | ENTRY DOORS.THE MINIMUM CODE |
| | REQUIREMENT IS A 45 MINUTE ASSEMBLY.IT |
| | IS ACCEPTABLE TO EXCEED CODE; HOWEVER, I |
| | AM BRINGING THIS TO YOUR ATTENTION. |
| | |
| | C. THE WINDOWS SPECIFIED ON THE PLAN ARE |
| | SINGLE HUNG.THIS DOES NOT COMPLY WITH |
| | THE REQUIREMENT "SHALL BE EQUIPPED WITH |
| | FIXED 3/4 HOUR ASSEMBLIES." |
| | |
| | D. SPECIFY FIRE RATING REQUIREMENT FOR |
| | THE WINDOWS. |
| | |
| | 3.)THE ENERGY CALCS WHICH WERE |
| | PREVIOUSLY SUBMITTED ARE NO LONGER IN |
| | THE PACKAGE. |
| | |
| | 4.)SEE PREVIOUS LIST, ITEM #10. |
| | POLICY IN REGARDS TO MISSILE IMPACT |
| | PROTECTION IS ATTACHED.THE PLAN NOW |
| | SPECIFIES ACCORDION SHUTTERS, BUT |
| | PRODUCT APPROVALS FOR GALVANIZED STEEL |
| | SHUTTERS WERE SUBMITTED.REMOVABLE |
| | SHUTTERS NOT ALLOWED FOR THE SECOND |
| | FLOOR, AND REMOVABLE SHUTTERS MUST BE |
| | APPROVED BY THE BUILDING OFFICIAL FOR |
| | THE FIRST FLOOR.ADDRESS. |
| | |
| | 5.)COMPLETE THE ATTACHED INSTALLATION |
| | SCHEDULE (SHUTTERS), OR PROVIDE ALL |
| | REQUIRED INFORMATION IN A SIMILAR |
| | FORMAT. |
| | |
| | 6.)PRODUCT APPROVALS FOR JELD-WEN |
| | DOORS WERE SUBMITTED.THERE ARE THREE |
| | DIFFERENT PRODUCT APPROVALS IN THE |
| | BROCHURE.SUBMIT ONLY THE DOOR YOU WILL |
| | INSTALL. |
| | |
| | 7.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED IN ADDITION TO NOAS |
| | SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 8.)SEE PREVIOUS LIST, ITEM #6. |
| | PROVIDE FIRE RATING INFORMATION FOR THE |
| | PRODUCT YOU ARE INSTALLING.THE PRODUCT |
| | APPROVALS FOR THE DOORS DO NOT INDICATE |
| | THAT THEY HAVE A FIRE RATING. |
| | |
| | 9.)SEE PREVIOUS LIST, ITEM #6.THE |
| | ENTRY DOORS ARE TO BE APPROVED BY |
| | HISTORIC PRIOR TO RESUBMITTAL AS PER |
| | THEIR LETTER DATED 11/20/03, WHICH IS NO |
| | LONGER IN THE PACKAGE. |
| | |
| | 10.)YOU HAVE DONE A CHANGE TO THE |
| | EXTERIOR OF THE BUILDING (ADDED |
| | ACCORDION SHUTTERS).THIS REQUIRES |
| | APPROVAL FROM HISTORIC PRESERVATION |
| | DEPARTMENT. |
| | |
| | 11.)PRODUCT APPROVAL FOR TRACO SINGLE |
| | HUNG EGRESS WINDOW WAS SUBMITTED.THIS |
| | IS ACCEPTABLE FOR THE WINDOWS WHICH ARE |
| | NOT REQUIRED TO BE FIRE RATED; HOWEVER, |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72.PLEASE PROVIDE. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 12.)PRODUCT APPROVALS AND FIRE RATING |
| | INFORMATION FOR THE FIRE RATED WINDOWS. |
| | |
| | 13.)SEE FBC905.2.2 IN REGARDS TO SMOKE |
| | DETECTOR REQUIREMENTS. |
| | |
| | 14.)SEE PREVIOUS LIST, ITEM #20, IN |
| | REGARDS TO VALUATION. |
| | |
| | 15.)SEE PREVIOUS TWO LISTS, ITEM #21, |
| | IN REGARDS TO ROOF DRAINS AND OVERFLOW |
| | DRAINS.SCUPPERS ARE SHOWN BUT NO |
| | INFORMATION PROVIDED IN REGARDS TO |
| | PRIMARY AND SECONDARY DRAINAGE SYSTEM. |
| | SEE FBC1503.4. |
| | |
| | 16.)PROVIDE A DETAIL FOR THE PRIMARY |
| | AND SECONDARY SCUPPERS, FBC1503.4, |
| | FBC1503.4.2. |
| | |
| | 17.)PROVIDE THE PARAPET WALL HEIGHT AS |
| | THIS INFORMATION IS REQUIRED TO |
| | DETERMINE DRAINAGE REQUIREMENTS. |
| | |
| | 18.)REVISE THE PERMIT APPLICATION |
| | DESCRIPTION OF WORK.THIS IS NOT ONLY |
| | AN INTERIOR REMODEL. |
| | |
| | 19.)SEE ELECTRIC REVIEW #2 AND THE |
| | ATTACHED FS553.80(2)(B).A 4X PLAN |
| | REVIEW FEE HAS BEEN CHARGED AS REQUIRED |
| | BY FLORIDA STATUTE.A RESUB FEE WILL |
| | NOT BE CHARGED.A BILL IS ATTACHED AND |
| | MUST BE PAID PRIOR TO RESUBMITTAL.THIS |
| | AMOUNT WILL CHANGE WHEN CORRECT |
| | VALUATION IS DETERMINED. |
| | |