2005-06-14 00:00:00*********** UNSAT2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW NOTES.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 OK, HOWEVER PLEASE SEE
 LOWER AREA FOR STAIRS NOW SHOWS A
 PC(PULL CHAIN)? FOR CONTROL OF EGRESS
 LIGHTING. PLEASE SEE A 3-WAY WP SWITCH
 IS REQUIRED.
 210.70,LS 101 5-8
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE
 COUNTERSPACE. SCALE FOR ELECTRICAL PLANS
 NOT PROVIDED, HOWEVER IF USEING 1/8" MIN
 PER CODE THERE APPEARS TO BE MISSING PER
 210.52C1. PLEASE SEE REDLINED PLANS.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE 210.8A6
 AS NOTED ON PREVIOUS NOTE.
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE #9 NO, PREVIOUS.
  
 10)NOTE: NOTE #10 NO, NEW SERVICE SHOWN,
 YET NO INFORMATION PROVIDED FOR EXISTING
 SERVICE, MAINS, GROUPING ETC. A NEW
 SERVICE WILL NOT BE PERMITTED.
 230.2
 PLEASE SEE 110.9, AIC RATING PROVIDED
 FOR PANEL, HOWEVER RATING FOR MAIN ALSO
 REQUIRED.
  
 11)NOTE: NOTE #11OK.
  
 12)NOTE: NOTE #12 OK, HOWEVER SEE NEW
 NOTES FOR OUTSIDE RECEPT.
  
 13)NOTE: NOTE #13 NO.
 PLEASE SEE PREVIOUS AND PLEASE SEE FAC
 61G1-16.004 FOR ALL INFORMATION REQUIRED
 ON TITLE BLOCK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE NEW GFI RECEPT FOR
 A/C COND IS NOW SHOWN CIRCUITED ON
 KITCHEN SMALL APPLIANCE CIRCUIT.PLEASE
 SEE 210.52B
  
 2)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR BLDG AND SCOPE OF WORK BRINGING BLDG
 UP TO CODE PER FBC CHAPTER 34.
 THIS WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS AND WORK ALSO REQUIRED
 IN OTHER PARTS OF STRUCTURE.
  
 3)NOTE: PLEASE SEE THE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO THE
 DESIGN PROFESSIONAL AND REPEAT COMMENTS
 FOR THE SAME CODE ARTICLES.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.\
 PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-06-13 00:00:00NOTES TO FOLLOW.