| 2005-06-14 00:00:00 | *********** UNSAT2ND REVIEW ********* |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE NEW NOTES. |
| | |
| | 1)NOTE: NOTE #1 OK. |
| | |
| | 2)NOTE: NOTE #2 OK, HOWEVER PLEASE SEE |
| | LOWER AREA FOR STAIRS NOW SHOWS A |
| | PC(PULL CHAIN)? FOR CONTROL OF EGRESS |
| | LIGHTING. PLEASE SEE A 3-WAY WP SWITCH |
| | IS REQUIRED. |
| | 210.70,LS 101 5-8 |
| | |
| | 3)NOTE: NOTE #3 OK. |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE |
| | COUNTERSPACE. SCALE FOR ELECTRICAL PLANS |
| | NOT PROVIDED, HOWEVER IF USEING 1/8" MIN |
| | PER CODE THERE APPEARS TO BE MISSING PER |
| | 210.52C1. PLEASE SEE REDLINED PLANS. |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SEE 210.8A6 |
| | AS NOTED ON PREVIOUS NOTE. |
| | |
| | 7)NOTE: NOTE #7 OK. |
| | |
| | 8)NOTE: NOTE #8 OK. |
| | |
| | 9)NOTE: NOTE #9 NO, PREVIOUS. |
| | |
| | 10)NOTE: NOTE #10 NO, NEW SERVICE SHOWN, |
| | YET NO INFORMATION PROVIDED FOR EXISTING |
| | SERVICE, MAINS, GROUPING ETC. A NEW |
| | SERVICE WILL NOT BE PERMITTED. |
| | 230.2 |
| | PLEASE SEE 110.9, AIC RATING PROVIDED |
| | FOR PANEL, HOWEVER RATING FOR MAIN ALSO |
| | REQUIRED. |
| | |
| | 11)NOTE: NOTE #11OK. |
| | |
| | 12)NOTE: NOTE #12 OK, HOWEVER SEE NEW |
| | NOTES FOR OUTSIDE RECEPT. |
| | |
| | 13)NOTE: NOTE #13 NO. |
| | PLEASE SEE PREVIOUS AND PLEASE SEE FAC |
| | 61G1-16.004 FOR ALL INFORMATION REQUIRED |
| | ON TITLE BLOCK. |
| | |
| | 14)NOTE: NOTE #14 OK. |
| | |
| | 15)NOTE: NOTE #15 OK. |
| | |
| | NEW NOTES: |
| | |
| | 1)NOTE: PLEASE SEE NEW GFI RECEPT FOR |
| | A/C COND IS NOW SHOWN CIRCUITED ON |
| | KITCHEN SMALL APPLIANCE CIRCUIT.PLEASE |
| | SEE 210.52B |
| | |
| | 2)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR BLDG AND SCOPE OF WORK BRINGING BLDG |
| | UP TO CODE PER FBC CHAPTER 34. |
| | THIS WILL HAVE A DIRECT AFFECT ON |
| | ELECTRICAL PLANS AND WORK ALSO REQUIRED |
| | IN OTHER PARTS OF STRUCTURE. |
| | |
| | 3)NOTE: PLEASE SEE THE ATTACHED COPY OF |
| | FS 553.80(2)(B) WITH RESPECT TO THE |
| | DESIGN PROFESSIONAL AND REPEAT COMMENTS |
| | FOR THE SAME CODE ARTICLES. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING.\ |
| | PLEASE SUBMIT ONE COPY OF OLD SHEETS FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-06-13 00:00:00 | NOTES TO FOLLOW. |