| 2005-06-11 00:00:00 | PERMIT #05021387 |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)HOW WILL THE OCCUPANCY SEPARATION |
| | BETWEEN THE FIRST AND SECOND FLOOR BE |
| | MAINTAINED AT THE BEARING WALL ON THE |
| | FIRST FLOOR? |
| | |
| | THE FOLLOWING COMMENTS REMAIN FROM THE |
| | PREVIOUS REVIEW.YOUR RESPONSE LETTER |
| | STATING THAT THESE ITEMS WILL BE |
| | ADDRESSED UNDER A SEPARATE PERMIT IS |
| | ACKNOWLEDGED.THE BOARD ORDER IS TO |
| | BRING THE ENTIRE BUILDING UP TO CODE |
| | COMPLIANCE.THIS CANNOT BE DONE UNDER |
| | SEPARATE PERMITS.IF THIS IS NOT |
| | ADDRESSED, THE DEMOLITION ORDER TO |
| | DEMOLISH THE BUILDING WILL BE REINSTATED |
| | AS PER BUILDING OFFICIAL. |
| | |
| | 3.)THE APPLICATION 03111034 INCLUDING |
| | ALL WORK TO BE PERFORMED TO BRING THE |
| | BUILDING UP TO CODE (FBC3401.7.2.6) HAS |
| | EXPIRED.THIS APPLICATION IS TO INCLUDE |
| | ALL WORK REQUIRED BY THE BOARD ORDER AND |
| | FBC3401.7.2.6.AS THE EXTERIOR IS NOT |
| | CURRENTLY CODE COMPLIANT, THIS CANNOT BE |
| | "INTERIOR RENOVATION ONLY" AS STATED ON |
| | THE APPLICATION AND PLANS. |
| | |
| | 4.)PROVIDE A FLOOR PLAN FOR THE FIRST |
| | FLOOR - ***NOTE***TO BE DONE AT A FUTURE |
| | DATE AS A TENANT BUILDOUT 8/8/05*** |
| | |
| | 5.)THE EXTERIOR STAIR IS TO COMPLY |
| | WITH FBC1006.2.4.PROVIDE ELEVATIONS |
| | AND INDICATE, TO SCALE, ALL OPENINGS |
| | WHICH REQUIRE FIRE RESISTANCE.SHOW ONE |
| | HOUR RATING REQUIRED ON THE PLAN. |
| | |
| | 6.)PROVIDE PRODUCT APPROVALS AND FIRE |
| | RATING INFORMATION FOR OPENINGS AFFECTED |
| | BY COMMENT #10.EXTERIOR DOORS ARE TO |
| | BE APPROVED BY HISTORIC PRESERVATION |
| | DEPARTMENT AS PER LETTER DATED 11/20/03. |
| | |
| | 7.)THE ENTRY DOOR IS REQUIRED TO HAVE |
| | A FIRE RATING AND A CLOSER, 1006.2.4. |
| | |
| | 8.) PROVIDE A SURVEY FOR THIS PROPERTY. |
| | CHECK FOR FBC TABLE 600 COMPLIANCE |
| | BEFORE RESUBMITTAL. |
| | |
| | 9.) BEDROOMS ARE REQUIRED TO HAVE |
| | EMERGENCY EGRESS, FBC1005.4.SHOW |
| | COMPLIANCE ON THE PLAN (WINDOW TYPE, |
| | SIZE AND SILL HEIGHT). |
| | |
| | 10.) SEE ATTCHED IMPLEMENTATIN STANDARD |
| | FOR HURRICANE MISSILE IMPACT PROTECTION, |
| | ITEM #13.IMPACT GLASS IS REQUIRED FOR |
| | THE SECOND FLOOR.NON IMPACT WITH |
| | SHUTTERS CAN BE APPROVED BY THE BUILDING |
| | OFFICIAL.A PLAN MUST BE SUBMITTED FOR |
| | REVIEW. |
| | |
| | 11.) SHOW TREAD AND RISER DIMENSIONS FOR |
| | THE EXTERIOR EGRESS STAIR, FBC1007.3. |
| | SHOW STAIR WIDTH. |
| | |
| | 12.) SHOW VERTICAL RISE FOR THE EXTERIOR |
| | STAIR, FBC1007.4. |
| | |
| | 18.) PROVIDE DETAILS FOR THE HANDRAIL |
| | AND GUARDRAIL, FBC1015, 1007.5.PROVIDE |
| | DESIGN CRITERIA FOR BOTH THE GUARDRAIL |
| | AND HANDRAIL FBC1608.2.DO NOT STATE |
| | CODE SECTION BY NUMBER; SPECIFY DESIGN |
| | CRITERIA.THIS COMMENT APPLIES TO BOTH |
| | THE HANDRAIL/GUARDRAIL AT THE STAIRS AND |
| | THE GUARDRAIL AT THE BALCONY. |
| | |
| | 19.) STAIRWAYS SHALL HAVE HANDRAILS ON |
| | EACH SIDE, FBC1007.5.2. |
| | |
| | 20.) ADJUST THE VALUE OF THE SCOPE OF |
| | WORK TO INCLUDE ALL WORK REQUIRED. |
| | |
| | 21.) SHOW COMPLIANCE WITH FBC1503.4, |
| | ROOF DRAINS AND FBC1503.4.2, OVERFLOW |
| | DRAINS.YOUR STATEMENT THAT THE WORK |
| | HAS BEEN COMPLETED IS ACKNOWLEDGED, BUT |
| | PLEASE SHOW CODE COMPLIANCE AS THIS WORK |
| | HAS NOT BEEN PERMITTED. |
| | |
| | 22.) THE PREVIOUS APPLICATION INCLUDED |
| | CONCRETE RESTORATION WORK.PROVIDE A |
| | SPECIFICATION AND LOCATION OF REPAIR |
| | WORK, OR INDICATE THAT THIS WORK IS NO |
| | LONGER NECESSARY. |