Plan Review Notes
Plan Review Notes For Permit 05021387
Permit Number 05021387
Review Stop B
Sequence Number 2
Notes
Date Text
2005-06-11 00:00:00PERMIT #05021387
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)HOW WILL THE OCCUPANCY SEPARATION
 BETWEEN THE FIRST AND SECOND FLOOR BE
 MAINTAINED AT THE BEARING WALL ON THE
 FIRST FLOOR?
  
 THE FOLLOWING COMMENTS REMAIN FROM THE
 PREVIOUS REVIEW.YOUR RESPONSE LETTER
 STATING THAT THESE ITEMS WILL BE
 ADDRESSED UNDER A SEPARATE PERMIT IS
 ACKNOWLEDGED.THE BOARD ORDER IS TO
 BRING THE ENTIRE BUILDING UP TO CODE
 COMPLIANCE.THIS CANNOT BE DONE UNDER
 SEPARATE PERMITS.IF THIS IS NOT
 ADDRESSED, THE DEMOLITION ORDER TO
 DEMOLISH THE BUILDING WILL BE REINSTATED
 AS PER BUILDING OFFICIAL.
  
 3.)THE APPLICATION 03111034 INCLUDING
 ALL WORK TO BE PERFORMED TO BRING THE
 BUILDING UP TO CODE (FBC3401.7.2.6) HAS
 EXPIRED.THIS APPLICATION IS TO INCLUDE
 ALL WORK REQUIRED BY THE BOARD ORDER AND
 FBC3401.7.2.6.AS THE EXTERIOR IS NOT
 CURRENTLY CODE COMPLIANT, THIS CANNOT BE
 "INTERIOR RENOVATION ONLY" AS STATED ON
 THE APPLICATION AND PLANS.
  
 4.)PROVIDE A FLOOR PLAN FOR THE FIRST
 FLOOR - ***NOTE***TO BE DONE AT A FUTURE
 DATE AS A TENANT BUILDOUT 8/8/05***
  
 5.)THE EXTERIOR STAIR IS TO COMPLY
 WITH FBC1006.2.4.PROVIDE ELEVATIONS
 AND INDICATE, TO SCALE, ALL OPENINGS
 WHICH REQUIRE FIRE RESISTANCE.SHOW ONE
 HOUR RATING REQUIRED ON THE PLAN.
  
 6.)PROVIDE PRODUCT APPROVALS AND FIRE
 RATING INFORMATION FOR OPENINGS AFFECTED
 BY COMMENT #10.EXTERIOR DOORS ARE TO
 BE APPROVED BY HISTORIC PRESERVATION
 DEPARTMENT AS PER LETTER DATED 11/20/03.
  
 7.)THE ENTRY DOOR IS REQUIRED TO HAVE
 A FIRE RATING AND A CLOSER, 1006.2.4.
  
 8.) PROVIDE A SURVEY FOR THIS PROPERTY.
 CHECK FOR FBC TABLE 600 COMPLIANCE
 BEFORE RESUBMITTAL.
  
 9.) BEDROOMS ARE REQUIRED TO HAVE
 EMERGENCY EGRESS, FBC1005.4.SHOW
 COMPLIANCE ON THE PLAN (WINDOW TYPE,
 SIZE AND SILL HEIGHT).
  
 10.) SEE ATTCHED IMPLEMENTATIN STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13.IMPACT GLASS IS REQUIRED FOR
 THE SECOND FLOOR.NON IMPACT WITH
 SHUTTERS CAN BE APPROVED BY THE BUILDING
 OFFICIAL.A PLAN MUST BE SUBMITTED FOR
 REVIEW.
  
 11.) SHOW TREAD AND RISER DIMENSIONS FOR
 THE EXTERIOR EGRESS STAIR, FBC1007.3.
 SHOW STAIR WIDTH.
  
 12.) SHOW VERTICAL RISE FOR THE EXTERIOR
 STAIR, FBC1007.4.
  
 18.) PROVIDE DETAILS FOR THE HANDRAIL
 AND GUARDRAIL, FBC1015, 1007.5.PROVIDE
 DESIGN CRITERIA FOR BOTH THE GUARDRAIL
 AND HANDRAIL FBC1608.2.DO NOT STATE
 CODE SECTION BY NUMBER; SPECIFY DESIGN
 CRITERIA.THIS COMMENT APPLIES TO BOTH
 THE HANDRAIL/GUARDRAIL AT THE STAIRS AND
 THE GUARDRAIL AT THE BALCONY.
  
 19.) STAIRWAYS SHALL HAVE HANDRAILS ON
 EACH SIDE, FBC1007.5.2.
  
 20.) ADJUST THE VALUE OF THE SCOPE OF
 WORK TO INCLUDE ALL WORK REQUIRED.
  
 21.) SHOW COMPLIANCE WITH FBC1503.4,
 ROOF DRAINS AND FBC1503.4.2, OVERFLOW
 DRAINS.YOUR STATEMENT THAT THE WORK
 HAS BEEN COMPLETED IS ACKNOWLEDGED, BUT
 PLEASE SHOW CODE COMPLIANCE AS THIS WORK
 HAS NOT BEEN PERMITTED.
  
 22.) THE PREVIOUS APPLICATION INCLUDED
 CONCRETE RESTORATION WORK.PROVIDE A
 SPECIFICATION AND LOCATION OF REPAIR
 WORK, OR INDICATE THAT THIS WORK IS NO
 LONGER NECESSARY.