| Plan Review Notes For Permit 05021387 |
| Permit Number |
05021387 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | | | | 1) SHT 5 0F 5 SANITARY RISER DIAGRAM | | | DOES NOT MEET CODE REQUIREMENTS, AND | | | SHALL BE IN AN ISOMETRIC FORM SHOWING | | | VENT CONNECTIONS. | | | 2) KITCHEN SINK IS NOT VENTED. SECTION | | | 901.2.1. | | | 3) TUB IN BATHROOM IS NOT VENTED. | | | SECTION 901.2.1. | | | 4) WASH MACHINE SHALL NOT DRAIN THROUGH | | | THE WET VENT OF THE BATHROOM FIXTURES, | | | BUT SHALL DISCHARGE DOWNSTREAM OF THE | | | BATHROOM FIXTURES. SECTION 909.1 | | | THE WASH MACHINE SHALL DISCHARGE INTO A | | | STANDPIPE AND A CLEANOUT 4' ABOVE THE | | | FLOOR IS REQUIRED. SECTIONS 1002.1 AND | | | 708.10. | | | 5) SEE ATTACHED SHEET FOR AN EXAMPLE OF | | | AN ISOMETRIC THAT MEETS CODE | | | REQUIREMENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|