Plan Review Notes
Plan Review Notes For Permit 05021387
Permit Number 05021387
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
 1) SHT 5 0F 5 SANITARY RISER DIAGRAM
 DOES NOT MEET CODE REQUIREMENTS, AND
 SHALL BE IN AN ISOMETRIC FORM SHOWING
 VENT CONNECTIONS.
 2) KITCHEN SINK IS NOT VENTED. SECTION
 901.2.1.
 3) TUB IN BATHROOM IS NOT VENTED.
 SECTION 901.2.1.
 4) WASH MACHINE SHALL NOT DRAIN THROUGH
 THE WET VENT OF THE BATHROOM FIXTURES,
 BUT SHALL DISCHARGE DOWNSTREAM OF THE
 BATHROOM FIXTURES. SECTION 909.1
 THE WASH MACHINE SHALL DISCHARGE INTO A
 STANDPIPE AND A CLEANOUT 4' ABOVE THE
 FLOOR IS REQUIRED. SECTIONS 1002.1 AND
 708.10.
 5) SEE ATTACHED SHEET FOR AN EXAMPLE OF
 AN ISOMETRIC THAT MEETS CODE
 REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]