| Plan Review Notes For Permit 05021387 |
| Permit Number |
05021387 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-21 00:00:00 | DENIED: | | | 1.PROVIDE DUCT SIZE ON THE SUPPLY | | | BRANCH DUCTS.RETURN AIR JUMPERS SHALL | | | BE A MINIMUM OF 1 1/2 TIMES GREATER THAN | | | THE CROSS SECTIONAL AREA (SQAURE INCHES) | | | OF THE SUPPLY AIR TO THAT ROOM. 2001 | | | FBC/M 601.4 EXCEPTION #1. | | | | | | 2.PROVIDE GRILLE SIZES. | | | | | | 3.PROVIDE INFORMATION & DETAILS FOR | | | THE DRYER EXHAUST.INDICATE DUCT | | | MATERIAL, SIZE, AND TERMINATION. | | | | | | 4.PROVIDE SCHEDULE FOR THE EXHAUST FAN | | | LOCATED IN THE BATHROOM. | | | | | | 5.PROVIDE ENERGY AND MANUAL J | | | CALCULATIONS IN ACCORDANCE WITH 2001 FBC | | | CHAPTER 13 SUB-SECTION 600. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|