2005-03-21 00:00:00DENIED:
 1.PROVIDE DUCT SIZE ON THE SUPPLY
 BRANCH DUCTS.RETURN AIR JUMPERS SHALL
 BE A MINIMUM OF 1 1/2 TIMES GREATER THAN
 THE CROSS SECTIONAL AREA (SQAURE INCHES)
 OF THE SUPPLY AIR TO THAT ROOM. 2001
 FBC/M 601.4 EXCEPTION #1.
  
 2.PROVIDE GRILLE SIZES.
  
 3.PROVIDE INFORMATION & DETAILS FOR
 THE DRYER EXHAUST.INDICATE DUCT
 MATERIAL, SIZE, AND TERMINATION.
  
 4.PROVIDE SCHEDULE FOR THE EXHAUST FAN
 LOCATED IN THE BATHROOM.
  
 5.PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORDANCE WITH 2001 FBC
 CHAPTER 13 SUB-SECTION 600.
  