Plan Review Notes
Plan Review Notes For Permit 05021387
Permit Number 05021387
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-03-23 00:00:001) PLEASE PROVIDE INFORMATION REGARDING
 OCCUPANCY USE FOR BOTH FLOORS OF THE
 BUILDING.
  
 2) PLEASE PROVIDE INTERIOR FINISH
 INFORMATION FOR WALLS AND CEILING.
  
 3) ABC TYPE FIRE EXTINGUISHERS MAY BE
 REQUIRED CONTINGENT ON ADDITIONAL
 OCCUPANCY INFORMATION.
  
 4)THE ENTRANCE DOOR THAT LEADS TO THE
 EXISTING STAIRS MUST COMPLY WITH NFPA
 101, SECTION 7.2.1.
  
 5) PLEASE BE ADVISED THAT ALL LIFE
 SAFETY MUST COMPLY WITH NFPA 101, 2003
 EDITION.
  
 6) PLEASE BE ADVISED THAT ALL
 DEMOLITION. RENOVATION AND CONSTRUCTURE
 SHALL BE IN ACCORDANCE WITH NFPA 241.
  
 7) PLEASE PROVIDE ADDITIONAL MEANS OF
 EGRESS INFORMATION ONCE THE EXISTING
 STAIRS ARE REACHED.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910