| Date |
Text |
| 2005-02-28 00:00:00 | ******** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE PROVIDE OCCUPANCY FOR |
| | FIRST FLOOR AREA AND USE. |
| | |
| | 2)NOTE: THE LAUNDRY CIRCUIT CALCULATION |
| | MUST COMPLY WITH 220.116(B).(1500 VA). |
| | |
| | 3)NOTE: PLEASE SEE 210.70, LS 101 5-8, |
| | PLEASE VERIFY MEANS OF EGRESS LIGHTING |
| | FROM SECOND FLR TO GRADE LEVEL. |
| | |
| | 3)NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | |
| | 4)NOTE: PLEASE SEE 210.11C1, TWO SM APPL |
| | CIRCUITS MIN. |
| | |
| | 5)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN |
| | COUNTERSPACE. |
| | |
| | 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 7)NOTE: PLEASE SEE 240.4B,310.16 FOR MIN |
| | SIZE AWG FOR RANGE ON A 2P-60A. |
| | |
| | 8)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| | FOR AHU. MIN 125%. PLEASE ALSO SEE |
| | 310.16/240.4 FOR SIZING OF AWG. |
| | PLEASE SEE 8KW SHOWN ON 2P30A AND #10. |
| | |
| | 9)NOTE: PLEASE SEE 210.52C3 FOR |
| | PENINSULAR GFI REQUIRED. |
| | |
| | 10)NOTE: PLEASE VERIFY IF PANEL IS NEW |
| | OR EXSITING. SHOWN AS NEW ANDNOTES |
| | MENTIONS NEW GROUND RODS ? |
| | PLEASE INCLUDE RISER DIAGRAM FOR FEED TO |
| | NEW PANEL. MAIN, GROUPING, GROUNDING, |
| | CONDUCTORS ETC. |
| | 215.5 |
| | PLEASE ALSO SUBMIT AIC RATING FOR NEW |
| | EQUIPMENT. 110.9. |
| | |
| | 11)NOTE: PLEASE INCLUDE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH A PANEL |
| | SCHEDULE. |
| | |
| | 12)NOTE: PLEASE SHOW AHU/A/C UNITS ALONG |
| | WITH REQUIRED DISC'S PER 440-11. |
| | PLEASE ALSO SEE 210.63 FOR REQUIRED GFI |
| | FOR COND UNIT. |
| | |
| | 13)NOTE: PLEASE CORRELATE ADDRESS ON |
| | PLANS AND APPLICATION. ONE MENTIONS, 800 |
| | SAPPODILLA, AND THE OTHER 633 37TH ST? |
| | PLEASE ALSO SEE BLDG REVIEW COMMENTS FOR |
| | SUITE # OR EXTENSION TO BLDG. |
| | |
| | 14)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 15)NOTE: PLEASE SEE NFPA-72 8-1.4.2, SD |
| | NOT PERMITTED IN KITCHEN. |
| | PLEASE ALSO SEE MIN DISTANCE SD IS |
| | REQUIRED TO BE FROM COOKING APPLIANCES |
| | WITH EXCEPTIONS. |
| | PLEASE ALSO SEE SD'S ARE ALSO REQUIRED |
| | TO BE A MIN OF 3' FROM BATH DOORS. |
| | |
| | |
| | PLEASE SEE OTHER POSSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT ONLY NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |