Plan Review Notes
Plan Review Notes For Permit 05021387
Permit Number 05021387
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-28 00:00:00******** UNSAT ***********
  
 1)NOTE: PLEASE PROVIDE OCCUPANCY FOR
 FIRST FLOOR AREA AND USE.
  
 2)NOTE: THE LAUNDRY CIRCUIT CALCULATION
 MUST COMPLY WITH 220.116(B).(1500 VA).
  
 3)NOTE: PLEASE SEE 210.70, LS 101 5-8,
 PLEASE VERIFY MEANS OF EGRESS LIGHTING
 FROM SECOND FLR TO GRADE LEVEL.
  
 3)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
  
 4)NOTE: PLEASE SEE 210.11C1, TWO SM APPL
 CIRCUITS MIN.
  
 5)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE.
  
 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 7)NOTE: PLEASE SEE 240.4B,310.16 FOR MIN
 SIZE AWG FOR RANGE ON A 2P-60A.
  
 8)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU. MIN 125%. PLEASE ALSO SEE
 310.16/240.4 FOR SIZING OF AWG.
 PLEASE SEE 8KW SHOWN ON 2P30A AND #10.
  
 9)NOTE: PLEASE SEE 210.52C3 FOR
 PENINSULAR GFI REQUIRED.
  
 10)NOTE: PLEASE VERIFY IF PANEL IS NEW
 OR EXSITING. SHOWN AS NEW ANDNOTES
 MENTIONS NEW GROUND RODS ?
 PLEASE INCLUDE RISER DIAGRAM FOR FEED TO
 NEW PANEL. MAIN, GROUPING, GROUNDING,
 CONDUCTORS ETC.
 215.5
 PLEASE ALSO SUBMIT AIC RATING FOR NEW
 EQUIPMENT. 110.9.
  
 11)NOTE: PLEASE INCLUDE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH A PANEL
 SCHEDULE.
  
 12)NOTE: PLEASE SHOW AHU/A/C UNITS ALONG
 WITH REQUIRED DISC'S PER 440-11.
 PLEASE ALSO SEE 210.63 FOR REQUIRED GFI
 FOR COND UNIT.
  
 13)NOTE: PLEASE CORRELATE ADDRESS ON
 PLANS AND APPLICATION. ONE MENTIONS, 800
 SAPPODILLA, AND THE OTHER 633 37TH ST?
 PLEASE ALSO SEE BLDG REVIEW COMMENTS FOR
 SUITE # OR EXTENSION TO BLDG.
  
 14)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 15)NOTE: PLEASE SEE NFPA-72 8-1.4.2, SD
 NOT PERMITTED IN KITCHEN.
 PLEASE ALSO SEE MIN DISTANCE SD IS
 REQUIRED TO BE FROM COOKING APPLIANCES
 WITH EXCEPTIONS.
 PLEASE ALSO SEE SD'S ARE ALSO REQUIRED
 TO BE A MIN OF 3' FROM BATH DOORS.
  
  
 PLEASE SEE OTHER POSSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  