| 2005-03-10 00:00:00 | PERMIT #05021387 |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)THE APPLICATION 03111034 INCLUDING |
| | ALL WORK TO BE PERFORMED TO BRING THE |
| | BUILDING UP TO CODE (FBC3401.7.2.6) HAS |
| | EXPIRED.THIS APPLICATION IS TO INCLUDE |
| | ALL WORK REQUIRED BY THE BOARD ORDER AND |
| | FBC3401.7.2.6.AS THE EXTERIOR IS NOT |
| | CURRENTLY CODE COMPLIANT, THIS CANNOT BE |
| | ?INTERIOR RENOVATION ONLY? AS STATED ON |
| | THE APPLICATION AND PLANS. |
| | |
| | 3.)THE PERMIT ISSUED FOR THE ROOF |
| | FRAMING (04050602) HAS EXPIRED.APPLY |
| | FOR A NEW PERMIT. |
| | |
| | 4.)NO INSPECTIONS HAVE BEEN DONE ON |
| | THE ROOF PERMIT ISSUED (04100264).THE |
| | WORK HAS BEEN COMPLETED AS PER |
| | CONVERSATION WITH THE CONTRACTOR. |
| | SCHEDULE INSPECTIONS AS REQUIRED BY |
| | FBC105(4).THIS PERMIT WILL EXPIRE |
| | APPROXIMATELY APRIL 7, 2005. |
| | |
| | 5.)INFORMATIONAL ONLY; THERE IS ALSO |
| | AN OPEN WINDOW PERMIT ON THIS JOB, |
| | 04070723. |
| | |
| | 6.)SHEET 2 OF 5 SHOWS A CHANGE TO THE |
| | EXTERIOR (REMOVAL AND REPLACEMENT OF |
| | WINDOWS).APPROVAL REQUIRED FROM THE |
| | HISTORIC PRESERVATION DEPARTMENT. |
| | |
| | 7.)DECLARE AN OCCUPANCY FOR THE FIRST |
| | FLOOR AND SECOND FLOOR, FBC CHAPTER 3. |
| | |
| | 8.)SHOW REQUIRED FIRE SEPARATION FBC |
| | TABLE 704.1 BETWEEN THE FIRST AND SECOND |
| | FLOOR, EITHER AS A RATED ASSEMBLY OR |
| | CALCULATED FIRE RESISTANCE FBC709. |
| | PROVIDE DETAILS FOR PENETRATIONS THROUGH |
| | THE FIRE RATED ASSEMBLY FBC705.6. |
| | |
| | 9.)PROVIDE A FLOOR PLAN FOR THE FIRST |
| | FLOOR. |
| | |
| | 10.)THE EXTERIOR STAIR IS TO COMPLY |
| | WITH FBC1006.2.4.PROVIDE ELEVATIONS |
| | AND INDICATE, TO SCALE, ALL OPENINGS |
| | WHICH REQUIRE FIRE RESISTANCE.SHOW ONE |
| | HOUR RATING REQUIRED ON THE PLAN. |
| | |
| | 11.)PROVIDE PRODUCT APPROVALS AND FIRE |
| | RATING INFORMATION FOR OPENINGS AFFECTED |
| | BY COMMENT #10.EXTERIOR DOORS ARE TO |
| | BE APPROVED BY HISTORIC PRESERVATION |
| | DEPARTMENT AS PER LETTER DATED 11/20/03. |
| | |
| | 12.)THE ENTRY DOOR IS REQUIRED TO HAVE |
| | A FIRE RATING AND A CLOSER, 1006.2.4. |
| | |
| | 13.) PROVIDE A SURVEY FOR THIS PROPERTY. |
| | CHECK FOR FBC TABLE 600 COMPLIANCE |
| | BEFORE RESUBMITTAL. |
| | |
| | 14.) BEDROOMS ARE REQUIRED TO HAVE |
| | EMERGENCY EGRESS, FBC1005.4.SHOW |
| | COMPLIANCE ON THE PLAN (WINDOW TYPE, |
| | SIZE AND SILL HEIGHT). |
| | |
| | 15.) WHERE WILL THE HURRICANE SHUTTERS |
| | BE STORED? |
| | |
| | 16.) SHOW TREAD AND RISER DIMENSIONS FOR |
| | THE EXTERIOR EGRESS STAIR, FBC1007.3. |
| | SHOW STAIR WIDTH. |
| | |
| | 17.) SHOW VERTICAL RISE FOR THE EXTERIOR |
| | STAIR, FBC1007.4. |
| | |
| | 18.) PROVIDE DETAILS FOR THE HANDRAIL |
| | AND GUARDRAIL, FBC1015, 1007.5.PROVIDE |
| | DESIGN CRITERIA FOR BOTH THE GUARDRAIL |
| | AND HANDRAIL FBC1608.2.DO NOT STATE |
| | CODE SECTION BY NUMBER; SPECIFY DESIGN |
| | CRITERIA.THIS COMMENT APPLIES TO BOTH |
| | THE HANDRAIL/GUARDRAIL AT THE STAIRS AND |
| | THE GUARDRAIL AT THE BALCONY. |
| | |
| | 19.) STAIRWAYS SHALL HAVE HANDRAILS ON |
| | EACH SIDE, FBC1007.5.2. |
| | |
| | 29.) ADJUST THE VALUE OF THE SCOPE OF |
| | WORK TO INCLUDE ALL WORK REQUIRED. |
| | |
| | 30.) SHOW COMPLIANCE WITH FBC1503.4, |
| | ROOF DRAINS AND FBC1503.4.2, OVERFLOW |
| | DRAINS. |
| | |
| | 31.) THE PREVIOUS APPLICATION INCLUDED |
| | CONCRETE RESTORATION WORK.PROVIDE A |
| | SPECIFICATION AND LOCATION OF REPAIR |
| | WORK. |
| | |
| | 32.) ENERGY CALCS REQUIRED, FBC13. |