| 2005-05-02 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | THE COMMENT NUMBER WILL REMAIN THE SAME |
| | AS THE PREVIOUS REVIEW: |
| | 3) SHT DA2.1 DEMO KEYNOTES D8 NOT FOUND |
| | ON SHEET. PLEASE CORRELATE NOTES WITH |
| | FLOOR PLAN. SECTION 104.2.1. - RESPONSE |
| | NOTED, BUT CHANGE TO BE MADE ON PLANS |
| | NOT ONLY ON COMMENT REPLY RESPONSE |
| | SHEET. |
| | 5) SHT A2.3 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106, & 1107 AND ALL |
| | SUBSECTIONS. SHOW LOCATION OF SECONDARY |
| | DRAINS FOR SOUTH PORTION. SHOW SIZE OF |
| | PRIMARY ROOF DRAINS AND SECONDARY ROOF |
| | DRAINS/SCUPPERS. SHOW SIZE OF GUTTERS |
| | AND DOWNSPOUTS AND INDICATE AREA BEING |
| | DRAINED BY EACH GUTTER AND DOWNSPOUT. |
| | SHOW SQUARE FOOTAGE FOR EACH ROOF AREA |
| | AND SHOW 1/2 AREA OF VERTICAL WALLS |
| | INCLUDING PARAPETS ADDED TO SF OF ROOF |
| | IN CALCULATIONS. SHOW SLOPE OF GUTTERS |
| | AND THE HIGH POINT ON EACH GUTTER. - |
| | RESPONSE NOTED, BUT PLANS INDICATE THAT |
| | THE GUTTERS AND DOWNSPOUTS SHALL BE |
| | REPLACED, AND SIZE OF EACH SHALL BE |
| | INDICATED AND CALCULATIONS SHALL BE |
| | GIVEN TO MAKE SURE SIZE OF GUTTERS AND |
| | DOWNSPOUTS IS CORRECT PER SECTIONS 1106 |
| | AND 1107. |
| | 8) SHT P1.1 PLUMBING NOTES: #13 AIR |
| | CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | REFERENCE. SECTION 604.9. #14 DIELECTRIC |
| | UNIONS ARE NOT APPROVED FOR DISTRIBUTION |
| | WATER. DIELECTRIC COUPLINGS ARE |
| | APPROVED. - RESPONSE NOTED AND ITS |
| | CORRECT THAT 604.9 DOES NOT PROHIBIT THE |
| | USE OF AIR CHAMBERS, THE CITY OF WEST |
| | PALM BEACH DOES NOT APPROVE OF AIR |
| | CHAMBERS UNLESS THEY HAVE A "BLEED OFF |
| | VALVE ON TOP OF THE AIR CHAMBER, A SHUT |
| | OFF VALVE AT THE BASE OF THE AIR CHAMBER |
| | AND A DRAIN VALVE TO DRAIN THE WATER |
| | FROM THE AIR CHAMBER TO RECHARGE THE AIR |
| | CHAMBER PER ATTACHED SHEET FROM PDI-WH |
| | 201 REPORT. ALSO AN ACCESS PANEL FOR |
| | EACH SET OF AIR CHAMBERS WILL BE |
| | REQUIRED FOR ACCESS TO THE VALVES ON THE |
| | AIR CHAMBERS. PDI-WH 201. - COMMENT #14 |
| | RESPONSE NOTED - DIELECTRIC UNIONS ARE |
| | NOT MADE FOR WATER DISTRIBUTION WATER, |
| | SO A DIELECTRIC COUPLING SHALL BE USED. |
| | 11) SHT P3.1 WATER PIPING DIAGRAM, AIR |
| | CHAMBERS ON BREAK ROOM SINK ARE NOT |
| | APPROVED. SECTION 604.9 DELETE FROM |
| | DIAGRAM. - RESPONSE NOTED. SEE COMMENT |
| | #8 AND IF THE VALVES, (3 EACH AIR |
| | CHAMBER), AND ACCESS PANEL WILL BE USED |
| | THAN THE AIR CHAMBERS WILL BE ALLOWED. |
| | PDI-WH 201. |
| | 13) ALL SHEETS SIGNED/SEALED/DATED BY AN |
| | ARCHITECT SHALL SHOW FIRM LICENSE NUMBER |
| | CERTIFICATE OF AUTHORIZATION. FAC |
| | 61G1-16.004(2) AND FS 481.219. - |
| | RESPONSE NOTED, BUT THE CA OR BUSINESS |
| | NUMBER IS NOT SHOWN IN THE TITLE BLOCK. |
| | |