| Date |
Text |
| 2005-04-20 00:00:00 | **** UNSAT 2ND REVIEW **** |
| | |
| | PLANS ONLY IN FOR "PLAN REVIEW" AND NOT |
| | SUBMITTED FOR PERMIT. |
| | |
| | 1NOTE: NOTE #1, NO, PLEASE SEE SAME |
| | ELECTRICAL SHEET WITH OUT ANY REFERENCE |
| | TO FBC 140 MPH . PLEASE ALSO SEE WE |
| | COULD NOT LOCATE WIND LOADING |
| | CALCULATIONS. |
| | |
| | 2)NOTE: NOTE #2 OK. |
| | |
| | 3)NOTE: NOTE #3 OK. |
| | |
| | 4)NOTE:NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE RISER |
| | STILL SHOWS AN EQUIPMENT GROUNDING |
| | CONDUCTOR INSTALLED BEFORE THE FIRST |
| | MEANS OF DISCONNECT. 250.6,250.24. |
| | |
| | 6)NOTE: NOTE #6 OK. |
| | OCP LOCATED AT PANEL. |
| | |
| | NEW NOTE: |
| | 1)NOTE:PLEASE SEE ELECTRICAL REVIEW |
| | PREVIOUS NOTES MENTIONS TO SEE OTHER ) |
| | PERTAINING TO POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S). PLEASE SEE NOTE #5 |
| | FROM PREVIOUS BLDG REVIEW WHICH |
| | REFERENCE WAS GIVEN TO FAC 61G1-16.004 |
| | AND FS 481.219 WITH INFORMATION REQUIRED |
| | ON TITLE BLOCKS. |
| | PLEASE SEE THIS IS REQUIRED ON ALL |
| | SHEETS AND FOR ALL TRADES WHEATHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | PLEASE SEE NONE OF THE TRADE SHEETS HAVE |
| | HAD TITLE BLOCKS CORRECTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |