| Plan Review Notes For Permit 05021334 |
| Permit Number |
05021334 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-21 00:00:00 | PROVISO: | | | 1.FRESH AIR INTAKES SHALL BE LOCATED A | | | MINIMUM OF 10 FT FROM PARKING LOTS PER | | | 2001 FBC/M 401.5.1. | | | | | | 2.RTU CURBS SHALL BE A MINIMUM OF 8" | | | ABOVE THE ROOF SURFACE IN ACCORDANCE | | | WITH 2001 FBC 1511.7. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|