| Date |
Text |
| 2005-03-02 00:00:00 | ***** UNSAT ***** |
| | |
| | ** PLEASE SEE PLANS ARE IN AS PROJECT |
| | FOR "PLAN REVIEW" ONLY NOT FOR PERMIT AT |
| | THIS TIME. |
| | |
| | 1)NOTE: PLEASE SEE WIND LOADING FOR |
| | POLES/ FIXTURES FOR SITE LIGHTING IS |
| | REQUIRED AT THIS TIME FOR BLDG REVIEW. |
| | MIN REQUIREMENTS FOR FBC 140 MPH. |
| | |
| | 2)NOTE:PLEASE SEE 300.22C FOR "AREAS |
| | USED FOR RETURN AIR" |
| | PLEASE SEE ALL UNDERGROUND CONDUITS |
| | ENTERING EQUIPMENT ETC OF PVC TYPE ARE |
| | NOT PERMITTED. |
| | PLEASE SPECIFY ON PLANS TYPE OF |
| | MATERIALS TO BE USED FOR CONDUIT ETC. |
| | IT IS NOTED OF MATERIALS TO BE RATED FOR |
| | PLENUM ABOVE CEILINGS. |
| | |
| | 3)NOTE: PLEASE PROVIDE RECEPTS ABOVE |
| | "SHOW WINDOWS". 210.62 THIS IS TO |
| | DISCOURAGE FLOOR RECEPTACLES AND |
| | UNSIGHTLY EXTENSION CORDS LIKELY TO |
| | CAUSE PHYSICAL INJURY, RECEPTACLES MUST |
| | BE INSTALLED DIRECTLY ABOVE A SHOW |
| | WINDOW, AND ONE RECEPTACLE IS REQUIRED |
| | FOR EVERY 12 LINEAR FT OR ?MAJOR |
| | FRACTION THEREOF? (6 FT OR MORE). SEE |
| | 220.3(B)(7) AND 220.12(A) FOR |
| | INFORMATION REGARDING LOAD COMPUTATIONS |
| | FOR SHOW WINDOWS. |
| | |
| | 4)NOTE: PLEASE SEE HANDRAWN ITEMS ON |
| | PLANS WHICH ARE SIGNED, DATED AND SEALED |
| | BY AN ARCH OR ENG ARE NOT PERMITTED. |
| | FS 471.025,481.221 |
| | |
| | 5)NOTE: PLEASE SEE THERE IS AN EQUIPMENT |
| | GROUNDING CONDUCTOR SHOWN FROM METER TO |
| | THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.6,250.24, THIS IS NOT |
| | PERMITTED . EQUIPMENT GRNDS ARE ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNETC. |
| | |
| | 6)NOTE: PLEASE VERFIY DISCONNECTING |
| | MEANS FOR WATER HEATER SHOWN UNDER SINK |
| | DOES NOT CONTAIN OCP. |
| | 110.26 WOULD APPLY IF OCP IS PROVIDED. |
| | THIS IS ONLY A NOTE. DISC APPEARS NOT TO |
| | CONTAIN OCP. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |