| 2005-03-18 00:00:00 | PERMIT #05021334 |
| | ****PAID PLAN CHECK**** |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 3.) THE OWNER IN OUR RECORDS |
| | (PRESIDENTIAL MOTORS) CONFLICTS WITH THE |
| | PERMIT APPLICATION. |
| | |
| | 4.) A0.1 REFERS TO ?WEST PALM BEACH |
| | COUNTY BUILDING CODE?.GOVERNING CODE |
| | IS FBC2001 WITH 2003 AMENDMENTS AND CITY |
| | OF WEST PALM BEACH AMENDMENTS. |
| | |
| | 5.) CERTIFICATE OF AUTHORIZATION |
| | REQUIRED FOR ENGINEERS AND ARCHITECTS; |
| | TITLE BLOCKS TO BE IN COMPLIANCE WITH |
| | BOARD RULES, FAC61G15-23.002, |
| | FAC61G1-16.003,004.PLEASE CHECK ALL |
| | SHEETS, INCLUDING CALCULATIONS. |
| | |
| | 6.) AWNING SHEETS (AB) AND CALCULATIONS |
| | DECLARE A ?WIND LOAD? OF 130MPH; CITY OF |
| | WEST PALM BEACH IS IN THE 140 MPH WIND |
| | ZONE. |
| | |
| | 7.) C2, ACCESSIBLE PARKING IS TO COMPLY |
| | WITH CITY OF WEST PALM BEACH STANDARDS, |
| | SEE ATTACHED. |
| | |
| | 8.) A1.1 REFERS TO DETAIL 12-A1.2, |
| | DUMPSTER ENCLOSURE PLAN.DETAIL IS NOT |
| | WHERE NOTED. |
| | |
| | 9.) PROVIDE AREA CALCULATIONS; EXISTING, |
| | PROPOSED, NEW TOTAL. |
| | |
| | 10.) FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED IN ADDITION TO TEST |
| | REPORTS.WWW.FLORIDABUILDING.ORG. |
| | STOREFRONT SYSTEM |
| | IMPACT PROTECTION |
| | STEEL ROOF DECK |
| | EXTERIOR DOOR |
| | |
| | 11.) IF REMOVABLE SHUTTERS ARE USED IN |
| | LIEU OF IMPACT GLASS, PROVIDE |
| | INFORMATION IN REGARDS TO WHERE THE |
| | SHUTTERS WILL BE STORED. |
| | |
| | 12.) PROVIDE WALL DIMENSION FOR DOOR 11, |
| | SHEET A2.1, PUSH SIDE, SEE FBC CHAPTER |
| | 11 TABLE 25 (A). |
| | |
| | 13.) DETAIL 3-A4.1, PROVIDE FASTENING OF |
| | WOOD BLOCKING TO COLUMNS. |
| | |