Plan Review Notes
Plan Review Notes For Permit 05021306
Permit Number 05021306
Review Stop B
Sequence Number 1
Notes
Date Text
2005-03-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SURVEY AND SITE PLAN DO NOT
 MATCH.
  
 2.)SEE FBC1005.4.5 IN REGARDS TO A
 MEANS OF ESCAPE IN THE EVENT OF A STORM.
 ALL DOORS ON THE PLAN ARE NON-IMPACT
 GLASS.PROVIDE AT LEAST ONE MEANS OF
 ESCAPE, INDICATE ON THE PLAN, AND
 PROVIDE COMPLIANT PRODUCT APPROVAL.
  
 3.)SEPARATE PERMIT REQUIRED FOR
 SHUTTERS AS NO SHUTTER INFORMATION HAS
 BEEN SUBMITTED AND IMPACT PROTECTION
 REQUIRED FBC1606.1.4.
  
 4.)PROVIDE FIRE RATING INFORMATION FOR
 THE GLASS BLOCK IF INSTALLED 0'-3' FROM
 THE PROPERTY LINE.
  
 5.)THE FLORIDA STATE PRODUCT APPROVAL
 SUBMITTED FOR THE "A & P CUSTOM WINDOW"
 (FIXED) IS PENDING.PROVIDE A CURRENT,
 APPROVED STATE OR LOCAL PRODUCT
 APPROVAL.
  
 6.)THE FASTENING FOR SOME OF THE
 CONNECTORS ON A5.1 CONFLICTS WITH THE
 PRODUCT APPROVAL.FASTENING MUST BE
 CONSISTENT WITH THE PAPERWORK ON THE
 STATE WEBSITE (WWW.FLORIDABUILDING.ORG)
 OR APPLY FOR A LOCAL PRODUCT APPROVAL.
 PLEASE FEEL FREE TO CONTACT ME IF YOU
 HAVE ANY QUESTIONS OR NEED ASSISTANCE.
  
 REGARDING TRUSS ENGINEERING PACKAGE
 (SPACE COAST TRUSS, INC.), SIGNED BY
 STEPHEN WARTER, PE:
  
 7.)NONCONCURRENT 10# LL FOR BOTTOM
 CHORD OF TRUSSES CANNOT BE USED (MUST BE
 CONCURRENT). NOTE 2 REFERS TO UBC94;
 GOVERNING CODE IS FBC2001.
  
 8.)THE TRUSS ENGINEERING (MITEK
 SOFTWARE) INCLUDES A 1.25 INCREASE FOR
 PLATES.THIS INCLUDES A STRESS INCREASE
 FOR STEEL WHICH IS NOT CODE COMPLIANT
 FBC1609.4.3(2).
  
 9.)PLEASE REVIEW OTHER TRUSS PACKAGES
 WHICH YOU MAY HAVE SUBMITTED ON OTHER
 PROJECTS IN THE CITY AND ARE
 NONCOMPLIANT, AND SUBMIT NEW ENGINEERING
 WHICH IS CODE COMPLIANT.
  
 10.)EITHER ALL SHEETS MUST BE SIGNED
 AND SEALED FOR THE TRUSS ENGINEERING OR
 AN INDEX SHEET IN COMPLIANCE WITH
 FAC61G15-31.003(5)(A) THROUGH (E).
  
 11.)THE SIGNATURE IS TO BE AN
 ORIGINAL,
 NOT A PHOTOCOPY, REQUIRES A DATE.TITLE
 BLOCK ALSO REQUIRED, FAC61G15-23.002.
  
 12.)TRUSS PLACEMENT IS TO BE SEALED BY
 THE TRUSS SYSTEM ENGINEER,
 FAC61G15-31.003(4).
  
  