Plan Review Notes
Plan Review Notes For Permit 05021275
Permit Number 05021275
Review Stop E
Sequence Number 1
Notes
Date Text
2005-03-01 00:00:00********* UNSAT ********
  
 1)NOTE: PLEASE SEE PLANS SEEM TO
 INDICATE COPIER DIRECTLY INFRONT OF
 ELECTRICAL PANELS?
 PLEASE NOTE/VERIFY IF PANELS FACE
 RECEPTION AREA?
 PLEASE SEE 110.26.
  
 2)NOTE: PLEASE PLACE NOTE NEXT TO NEW
 METER FOR "FLOATING NEUTRAL". PLEASE SEE
 250.6,250.24.
  
 3)NOTE: PLEASE PROVIDE LOAD CALCULATION
 FOR EXISTING GUTTER/400A MAIN FEEDING
 GUTTER.
 215.5/220
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE OLD/VOIDED SHEETS FROM
 SETS AND INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SEE ONE SET OF OLD SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  