Plan Review Notes
Plan Review Notes For Permit 05021273
Permit Number 05021273
Review Stop E
Sequence Number 4
Notes
Date Text
2005-08-15 00:00:00***** UNSAT***
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW.
  
  
 1)NOTE: PLEASE SEE VALUATION FOR SCOPE
 OF WORK WAS NOT UP DATED. NOTE ON REV
 COVER SHEET MENTIONS THIS WILL BE PAID
 UPON ISSUANCE. PLEASE SEE PERMIT WAS
 ISSUED PREVIOUSLY.
 PLEASE SEE BLDG VALUATION MAY BE
 ASSESSED BY BLDG PLANS REVIEW.
 FBC 104.6.5
 CITY OF WEST PALM BEACH AMENDMENTS.
  
 2)NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS
 REVIEW. PLEASE SEE RISER IS UNCLEAR FOR
 SCOPE OF WORK IN ADJACENT MECH/ELEC RM.?
 PLEASE SEE ORIG PLANS SUBMITTED AND
 THESE PLANS APPEAR TO SHOW ONLY
 "DARKENED" LINES ON RISER TO BE INCLUDED
 IN SCOPE OF WORK FOR THIS PERMITAND
 PROJECT. PLEASE SEE OTHER AREAS OF RISER
 ARE BEING REVISED ON EACH SUBMITTED
 REVISIONS?
 PLEASE SEE PREVIOUS PLANS SHOWED TWO
 DISC'S, ONE NEW, ONE FUTURE, HOWEVER
 THESE WERE NOT "DARKENED" AS NEW WORK IS
 NOTED. PLEASE SEE THIS REVISION NOW
 MENTIONS THIS WORK ON RISER AS
 "EXISTING".
 IT IS UNCLEAR HOW INFORMATION IS REVISED
 WHEN NOT INCLUDED IN THE SCOPE OF THIS
 PERMIT??
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED RESPONSE LTR TO CLARIFY:
 WHICH WORK ISBEING DONE UNDER THIS
 PERMIT?
 WHICH WORK IS NEW?
 WHICH IS EXSITING AND NOT INCLUDED IN
 THIS SCOPE.
  
 3)NOTE: PLEASE SEE LIGHTING LOADS DO NOT
 SEEMED TO HAVE BEEN INCREASED DUE TO
 ADDED SQ FT FOR TENANT.?
 220.3
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY SUBMITNEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD/VOIDED SHEETS MAY BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]