2005-11-21 00:00:00DENIED;
 1.PAGE P-1 CLEAR FLOOR SPACE MUST BE A
 FORWARD APPROACH, PLAN INDECATE A SIDE
 APPROACH. SEE FBC-2001 CHAPTER 11
 SEC.11-4.24.5.
 2.RE-DUE INT. ELEVATION ON SHEET A-1.1
 SHOWING LOCATION OF NEW SEWAGE EJECTOR.
 NEW EQUIPMENT TO BE INSTALLED MUST NOT
 RESTRICT THE FORWARD APPROACH OR THE
 CLEAR FLOOR SPACE. SEE SEC. 11-4.24.3
 AND 11-4.24.5.
 PLUMBING PLAN REVIEW BY;