| Plan Review Notes For Permit 05021273 |
| Permit Number |
05021273 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-07-05 00:00:00 | ******DENIED****** | | | | | | 1) IN ACCORDANCE WITH LOCAL FIRE CODE | | | REQUIREMENTS, NEW DUCT SMOKE DETECTOR | | | INSTALLATIONS SHALL BE WIRED INTO THE | | | FIRE ALARM SYSTEM TO SOUND A GENERAL | | | FIRE ALARM WHEN ACTIVATED. | | | | | | 2) PLEASE NOTE THAT SHEETS FP-1 AND FP-2 | | | DON'T ILLUSTRATE ANY REVISIONS OR | | | UPDATED CHANGES IN THE TITLE BLOCK. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR THE FIRE SPRINKLER AND | | | FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 805-6722 OR 835-2951 |
|