Plan Review Notes
Plan Review Notes For Permit 05021273
Permit Number 05021273
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2005-07-05 00:00:00******DENIED******
  
 1) IN ACCORDANCE WITH LOCAL FIRE CODE
 REQUIREMENTS, NEW DUCT SMOKE DETECTOR
 INSTALLATIONS SHALL BE WIRED INTO THE
 FIRE ALARM SYSTEM TO SOUND A GENERAL
 FIRE ALARM WHEN ACTIVATED.
  
 2) PLEASE NOTE THAT SHEETS FP-1 AND FP-2
 DON'T ILLUSTRATE ANY REVISIONS OR
 UPDATED CHANGES IN THE TITLE BLOCK.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951