2005-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT A1.0 NO DEAD ENDS ALLOWED SECTION
 704.5. FIELD INSPECTOR SHALL INSPECT THE
 DEMO OF THE EXISTING SINK PRIOR TO
 COVERING.
 2. SHT A1.1 BREAK ROOM SINK SHALL BE
 ACCESSIBLE. PLEASE SHOW THE FOLLOWING ON
 THE FLOOR PLAN AND THE DETAIL:
 A. KNEE CLEARANCE 11-4.24.3
 B. SINK DEPTH 11-4.24.4
 C. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 PROVIDED FOR FORWARD APPROACH AND SHALL
 ENTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. ALSO NO CABINET DOORS SHALL BE
 ALLOWED IN THE CLEAR FLOOR SPACE FOR THE
 SINK.
 D. EXPOSED PIPES & SURFACES 11-4.24.6
 E. FAUCETS 11-4.24.7
 SHOW COMPLIANCE WITH ALL THE ABOVE.
 3. SHT P-1 WATER ISOMETRIC. WATER HAMMER
 ARRESTORS ARE REQUIRED FOR ALL QUICK
 CLOSING VALVES, SUCH AS ICE MAKERS, DISH
 WASHERS AND/OR WASH MACHINES. THEY SHALL
 BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING PER
 PDI-WH 201.
  