| 2005-03-03 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05021224 |
| | ADD: 1300 S DIXIE HWY |
| | CONT:RAPP CONSTRUCTION |
| | TEL: (561)248-6411 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)PROVIDE NOC RECORDED WITH THE CLERK OF |
| | COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) SEE ELECTRICAL COMMENTS AS ENGINEERS |
| | FULL SIGNATURE, 471.025.PLANS, |
| | SPECIFICATIONS,REPORTS OR OTHER |
| | DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 3) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PLANS INDICATE WORK TO BE ACCOMPLISHED |
| | UNDER THIS PERMIT " SECOND FLOOR |
| | GRAPHICS HALL" BUT SHEET A-4.1.1 |
| | INDICATES WORK ON THE FIRST FLOOR BACK |
| | STAGE COORIDOR 126 AND STORAGE AREA, IS |
| | THERE WORK TO BE COMPLETED UNDER THIS |
| | PERMIT OR ELSEWHERE ON THE FIRST FLOOR? |
| | |
| | 4) PLANS (A-321) INDICATE WORK IN |
| | HALLWAY # 204, SEE SECTION 1021.4 DOORS |
| | SWINGING INTO A CORRIDOR SHALL BE |
| | RECESSED TO PREVENT INTERFERENCE WITH |
| | CORRIDOR TRAFFIC OR SWING OPEN 180 |
| | DEGREES. DOORS IN ANY POPSITION SHALL |
| | NOT REDUCE THE CORRIDOR WIDTH BY MORE |
| | THAN ONE HALF. |
| | |
| | 5A) A-2.2.3 NOTE# 7 REFERS TO LIFE |
| | SAFETY PLAN FOR LOCATION AND DETAILS OF |
| | 1-HR RATED CEILING ABOVE 2X2 ACT |
| | CEILING, CAN NOT FIND THE LIFE SAFETY |
| | PLAN REFRENCED. |
| | 5B) DIRECTLY BELOW THIS NOTE IS A |
| | DESIGNATION FOR A 1 HR RATED WALL, WALL |
| | IS NOT SHOWN ON PLANS. |
| | |
| | 6) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PLANS DO NOT INDICATE THE MINIMUM BLDG |
| | TYPE OR IF 1HR PROTECTED OR FIRE |
| | SPRINKLERED? |
| | |
| | 7)1005.4 EMERGENCY ESCAPE AND RESCUE |
| | OPENINGS, (2) EVERY ROOM OR SPACE |
| | GREATER THAN 250 FT USED FOR CLASSROOM |
| | OR OTHER ED- UCATIONAL PURPOSES OR |
| | NORMALLY SUBJECT TO STUDENT OCCUPANCY, |
| | AND EVERY ROOM SUBJECT TO CLIENT |
| | OCCUPNCY SHALL NOT HAVE NOT LESS THAN |
| | ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE, |
| | SEE EXCEPTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | BUILDING PLAN REVIEW |