| Plan Review Notes For Permit 05021213 |
| Permit Number |
05021213 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-08-10 00:00:00 | MECHANICAL REVISION | | | *** DENIED *** | | | 1) ARCHITECT NEEDS TO SIGN AND DATE EACH | | | CHANGE MADE TO PLANS AFTER HE SEALED | | | THEM. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT, PER 2004 FBC | | | 13-600.3.ABC.2 . ALSO NEED TO SUBMIT TWO | | | COPYS OF THE ENERGY CALCULATIONS. | | | | | | 3) PLEASE SUBMIT DETAILED MANUFACTURE'S | | | SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS FOR GAS HYDRONIC SPACE & | | | WATER HEAT, AS INDICATED ON ENERGY CAL'S | | | 13A. | | | | | | 4) PROVIDE COMBUSTION AIR FOR GAS WATER | | | HEATER, AS INDICATED ON ENERGY CAL'S 14A | | | & B, PER 2001 FBC/M 701 . | | | | | | 5) SHOW LOCATION OF 5.3 GAL. WATER | | | HEATER, AS INDICATED ON ENERGY CAL'S | | | 14B. | | | | | | 6) 14X8 SUPPLY AIR TRUNK LINE TO AHU #1 | | | IS TO SMALL FOR A 4 TON A/C SYSTEM. | | | PLEASE SUBMIT MANUAL D CALCULATIONS FOR | | | RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R | | | M1601.1 AND FBC 13-610.1.ABC.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|