Plan Review Notes
Plan Review Notes For Permit 05021213
Permit Number 05021213
Review Stop E
Sequence Number 5
Notes
Date Text
2006-07-26 00:00:00*** REDLINED ****
  
 1) NOTE: PLEASE SEE GROUNDING ELECTRODE
 AT MAINHOUSE STILL REQUIRED PER
 250.32,250.50
  
 2) NOTE: PLEASE SEE GARAGE SHOWS AN AHU,
 YET NO CU IS SHOWN? THIS MAY BE SPLIT
 FROM THE CU'S AT MAIN HOUSE, VERIFY.
 PLEASE ALSO SEE MAIN HOUSE SHOWS A THIRD
 A/C IN CLOSET OF UTILITY ROOM?? VERIFY.
 IS THIS ALSO AN ADDITIONAL A/C SPLIT
 FROM OTHERS?
  
 3) NOTE: PLEASE PANEL "B" SHOWS POOL
 HEATER , YET NO ELEC STUB OUT SHOWN OR
 FUTURE LOCATION SHOWN.
 THIS IS ALSO TO VERIFY.
  
 4) NOTE: PLEASE SEE SD IN MASTER BED RM
 SHALL BE MOVED TO BE WITHIN 12" OF THE
 HIGHEST POINT ON A FLAT CEILING.
 NFPA-72 11.8.3
  
  
 ** PLEASE VERIFY THE ABOVE AND MAKE ANY
 CHANGES NEEDED BEFORE ROUGH.
  