| Plan Review Notes For Permit 05021213 |
| Permit Number |
05021213 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-07-26 00:00:00 | *** REDLINED **** | | | | | | 1) NOTE: PLEASE SEE GROUNDING ELECTRODE | | | AT MAINHOUSE STILL REQUIRED PER | | | 250.32,250.50 | | | | | | 2) NOTE: PLEASE SEE GARAGE SHOWS AN AHU, | | | YET NO CU IS SHOWN? THIS MAY BE SPLIT | | | FROM THE CU'S AT MAIN HOUSE, VERIFY. | | | PLEASE ALSO SEE MAIN HOUSE SHOWS A THIRD | | | A/C IN CLOSET OF UTILITY ROOM?? VERIFY. | | | IS THIS ALSO AN ADDITIONAL A/C SPLIT | | | FROM OTHERS? | | | | | | 3) NOTE: PLEASE PANEL "B" SHOWS POOL | | | HEATER , YET NO ELEC STUB OUT SHOWN OR | | | FUTURE LOCATION SHOWN. | | | THIS IS ALSO TO VERIFY. | | | | | | 4) NOTE: PLEASE SEE SD IN MASTER BED RM | | | SHALL BE MOVED TO BE WITHIN 12" OF THE | | | HIGHEST POINT ON A FLAT CEILING. | | | NFPA-72 11.8.3 | | | | | | | | | ** PLEASE VERIFY THE ABOVE AND MAKE ANY | | | CHANGES NEEDED BEFORE ROUGH. | | | |
|