| Plan Review Notes For Permit 05021213 |
| Permit Number |
05021213 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-05-09 00:00:00 | ********* REDLINEDNOTES ********** | | | | | | 1)PLEASE SEE COOKTOP STILL SHOWN AS 8KW | | | W/ 30A OCP. | | | 2)NOTE: MOVED GROUNDING ELECTRODE SYSTEM | | | FOR "MAIN HOUSE" PANEL. SHOWN TO GARAGE | | | PANEL, MOVED TO MAIN HOUSE PER 250.32 | | | 3)ARC FAULT PROTECTION FOR BEDROOM | | | CIRCUITS NOTED FOR RECEPTS AND LTS, | | | PLEASE SEE 210.12 2002 NEC, "ALL | | | OUTLETS" INCLUDING SD'S,FANS ETC TO BE | | | ARC FAULT. | | | | | | | | | THE ABOVE ITEMS WERE REDLINED ON BOTH | | | SETS OF PLANS AND DO NOT NEED TO BE | | | REVISED. IF REVISIONS ARE MADE TO PLANS | | | AT ANY TIME DURING CONSTRUCTION, PLEASE | | | MAKE THE ABOVE CORRECTIONS. |
|