| Plan Review Notes For Permit 05021213 |
| Permit Number |
05021213 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-04-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA STATUTES | | | | | | 1) SHT A-4 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. CORRECT THE | | | FOLLOWING: | | | A. FROM PREVIOUS REVIEW, ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUPS | | | SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF | | | THE WET VENT. SECTION 909.1 (THE SECOND | | | FLOOR W/M IS DRAINING THROUGH THE WET | | | VENT FOR FIRST FLOOR BATHROOM). | | | B. NEW COMMENT, SHOWER NOT VENTED IN | | | BATHROOM #3. SECTION 901.2.1. | | | C. VENT FOR KITCHEN SINK SHOWN AS VENT | | | THRU ROOF, BUT FLOOR PLAN SHOWN AS 1/2 | | | WALL. PLEASE CLARIFY. SEC 104.2.1. | | | 2) SEE EXAMPLES IN RED FOR A RISER THAT | | | MEETS CODE REQUIREMENTS. | | | 3) SEE ELECTRICAL REVIEW AND ATTACHED | | | SHEET CONCERNING FS 553.80(2)(B) AND THE | | | DESIGN PROFESSIONAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|