Notes
Date Text
2005-04-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA STATUTES
  
 1) SHT A-4 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. FROM PREVIOUS REVIEW, ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS
 SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. SECTION 909.1 (THE SECOND
 FLOOR W/M IS DRAINING THROUGH THE WET
 VENT FOR FIRST FLOOR BATHROOM).
 B. NEW COMMENT, SHOWER NOT VENTED IN
 BATHROOM #3. SECTION 901.2.1.
 C. VENT FOR KITCHEN SINK SHOWN AS VENT
 THRU ROOF, BUT FLOOR PLAN SHOWN AS 1/2
 WALL. PLEASE CLARIFY. SEC 104.2.1.
 2) SEE EXAMPLES IN RED FOR A RISER THAT
 MEETS CODE REQUIREMENTS.
 3) SEE ELECTRICAL REVIEW AND ATTACHED
 SHEET CONCERNING FS 553.80(2)(B) AND THE
 DESIGN PROFESSIONAL.
  
 REVIEW BY KEN STEVENS