Plan Review Notes
Plan Review Notes For Permit 05021213
Permit Number 05021213
Review Stop M
Sequence Number 2
Notes
Date Text
2005-04-21 00:00:00MECH. PLAN REVIEW.
 PROVISO:
 1. SECOND FLOOR MASTER BATH REQUIRES
 EXHAUST FAN IN MAIN ROOM AREA. 2003
 FBC/M 402.2.3.1 .
 2. FIRST FLOOR STUDY, REQUIRES NINE
 INCH DUCT R/AWITH A SUPPLY OF SEVEN
 INCH. 2003 FBC/M 601.4 EXCEPTION 1.
 BALLANCED RETURN AIR .
 3. AHU,S REQUIRE AUXILIARY DRANE PAN
 WITH OVERFLOW PROTECTION. 2001. FBC/M
 307.2.3 .
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.