Plan Review Notes
Plan Review Notes For Permit 05021213
Permit Number 05021213
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-20 00:00:00************ UNSAT ***************
  
 PLEASE SEE MANY NOTES FROM PREVIOUS
 REVIEW STILL HAVE NOT BEEN CORRECTED.
 PLEASE ALSO SEE SOME NEW NOTES DUE TO
 OTHER CHANGES IN PLANS.
  
 THESE NOTES ARE LISTED DIRECTLY IN
 NUMBERED ORDER FROM PREVIOUS REVIEW.
  
 1)NOTE: NOTE #1 NO, PLEASE SEE MOST OF
 NOTE HAS NOT BEEN CHANGED OR ADDRESSED.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO,
 PLEASE SEE GROUPING OF MAINS, MEANS OF
 DISCONNECT FOR DEATCHED BLDGS ETC.
 225.31-225.36, 250.32 ETC.
  
 4)NOTE: NOTE #4 NO, UNABLE TO VERIFY
 ACTUAL INSTALLATION OF SERVICE DUE TO
 MISSING INFORMATION, NOT CORRECTED
 INFORMATION.215.5, 250.50.250.32
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 NO, PLEASE SEE PANEL
 SCHEDULE(S), ITEMS STILL NEED TO BE
 ADDRESSED.
 SEE REDLINES.
  
 8)NOTE: NOTE #8 NO, SEE PANEL SCHEDULE,
 AND VERIFY LABLELING OF SMALL APPL AND
 ALSO LOAD FOR SM APPL. 210.11C1,220.16
 ETC.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 NO. SEE PREVIOUS.
  
 12)NOTE: NOTE #12 NO, PLEASE SEE MISSING
 TWO PER 210.52, REDLINED.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK, HOWEVER,SEE NEXT
 NOTE.
  
 15)NOTE: NOTE #15 OK, HOWEVER PLEASE SEE
 NOW BOTH AHU'S AHVE BEEN ADDED TO
 CLOTHES CLOSET. PLEASE SEE DISC MEANS
 SHALL CONTAIN NO OCP. ALL CLEARENCE
 REQUIREMENTSETC. PER 110.26??
 PLEASE VERIFY IF THESE ARE INSTALLED IN
 ATTIC SPACE.?
  
 16)NOTE: NOTE #16 NO.
 PLEASE ALSO SEE NOTE ADDED TO E-2 DOES
 NOT MEET 2002 NEC 210.12
 SEE SAME AS PREVIOUS REVIEW.
  
 17)NOTE: NOTE #17 OK , HOWEVER PLEASE
 VERIFY FIXTURE TYPE AND WATTAGE. PLEASE
 SEE "MOST" "AIR-TITE" CANS WHICH ARE
 REQUIRED UNDER FLORIDA ENERGY CODE
 CONTAIN A MAX OF 75W PER FIXTURE.
 PLEASE VERIFY.
  
 18)NOTE: NOTE #18, NO. NO CORRECTIONS
 MADE.
  
 19)NOTE: NOTE #19 OK.
  
 20)NOTE: NOTE #20 NO.
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 NO, PLEASE SEE NO GFI
 PROTECTION INDICATED. 680.24
  
 23)NOTE: NOTE #23 OK.
  
 24)NOTE: NOTE #24 NO. SEE PREVIOUS
 REVIEW.
  
 25)NOTE: NOTE #25 NO RESPONSE REQUIRED.
  
  
 *** NEW NOTES***
  
 1)NOTE: PLEASE SEE UNDER FBC
 DEFINITIONS, A BREEZEWAY OF THIS SIZE
 DOES NOT CONSIDER THIS TO BE "ONE" BLDG.
 PLEASE SEE NEC 225 ETC AS PREVIOUSLY
 NOTED ABOVE FOR DETACHED BLDGS.
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 THE DESIGN PROFESSIONAL.
 PLEASE BE INFORMED IF PLANS COME BACK
 WITH "ANY" OF THE NOTES FROM PREVIOUS
 TWO REVIEWS NOT ADDRESSED, A 4X FEE
 SHALL BE ACCESSED FOR PLAN REVIEW
 PORTION WHICH IS 30% OF PERMIT FEE TIMES
 4(FOUR).
 ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED FOR FILE AS ON PREVIOUS REVIEW.
  
  
 3)NOTE: PLEASE SEE MANY OF THE ABOVE
 ITEMS WERE REDLINED AS WAS DONE ON
 PREVIOUS REVIEW TOHELP WITH LOCATIONS
 OF COMMENTS.
  
 4)NOTE: PLEASE REMOVE ALL OLD/ VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE ONLY SUBMIT ONE SET OF VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717