| Plan Review Notes For Permit 05021213 |
| Permit Number |
05021213 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-11 00:00:00 | 3/11/05 DENIED GS | | | | | | FBC 2001 SEC 909 | | | 1-ONLY THE FIXTURES WITHIN THE BATHROOM | | | GROUPS SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN.ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF | | | THE WET VENT. | | | 2-DOWNSTAIRS WC AND SHR. NOT VENTED |
|