| 2005-03-01 00:00:00 | ************ UNSAT *************** |
| | |
| | 1)NOTE: PLEASE CORRELATE PLANS/ PANEL |
| | SCHEDULE(S) AND RISER DIAGRAM. |
| | PLEASE SEE RISER MENTIONS 200A PANEL |
| | WITH SUB PANEL. NOTES MENTIONS 2-200A |
| | PANELS WITH 400A MCB AND 60A SUB POOL |
| | PANEL, HOWEVER PANELS AR BOTH SHOWN AS |
| | 150A? |
| | PLEASE ALSO SEE #6'S FOR SUB PANEL, YET |
| | SUB PANEL IS 150A W/ 106A'S OF LOAD? |
| | PLEASE SEE PANEL "A" DOES NOT INDICATE |
| | ANY SUB-PANEL FEED? |
| | PLEASE SEE RISER ALSO SHOWS A 6/0 FOR |
| | EQUIPMENT GROUNDING CONDUCTOR. |
| | (MISPRINT)? |
| | ETC ETC. |
| | |
| | 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3)NOTE: PLEASE SHOW LOCATION OF ALL |
| | PANELS, DISCONNECTS ON PLANS. |
| | 215.5 |
| | PLEASE VERIFY IF GARAGE IS GOING TO HAVE |
| | A SUBPANEL? |
| | |
| | 4)NOTE: PLEASE VERIFY IF FOOTER STEEL IS |
| | GOING TO BE BONDED FROM MAIN HOUSE FOR |
| | GROUNDING ELECTRODE SYSTEM. |
| | PER 250.50,250.32? |
| | |
| | 5)NOTE: PLEASE LABEL PANELS ON RISER TO |
| | CORRELATE WITH PANELS. |
| | |
| | 6)NOTE: PLEASE CORRELATE MECHANICAL |
| | PLANS WITH ELECTRICAL PLANS. MECH SHOWS |
| | BOTH HEAT-STRIPS AS 10KW, HOWEVER |
| | ELECTRICAL PLANS INDICATES 1-10KW AND |
| | 1-5KW. |
| | |
| | 7)NOTE: PLEASE SEE PANEL SCHEDULES, |
| | THERE ARE NUMEROUS ITEMS WHERE OCP, AWG |
| | AND KW/LOADS DO NOT MEET CODE. |
| | 50A BRKR ON #12 |
| | 10A BRKR? W/ 5KW LOAD |
| | 50A BRKR FOR SM APLL CIRCUITS. |
| | 60A BRKR FOR 5KW HEAT. |
| | ETC ETC. |
| | |
| | 8)NOTE: PLEASE SEE 210.11C1 AND 220.16 |
| | FOR MIN TWO OR MORE SMALL APPLIANCE |
| | CIRCUITS.SEE PREVIOUS NOTE. |
| | |
| | 9)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 10)NOTE: PLEASE SHOW ALL GARAGE RECEPTS |
| | AS GFI/GFI PROTECTED. 210.8 |
| | |
| | 11)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | MUST BE 20A AND #12 |
| | |
| | 12)NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | THERE ARE NUMEROUS RECEPTS MISSING. |
| | |
| | 13) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | MISSING REAR, PLEASE ALSO INDICATE AS |
| | GFI. |
| | |
| | 14)NOTE: PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 15)NOTE: PLEASE SEE MISSING A/C COND |
| | UNIT EQUIPMENT ON PLANS. |
| | PLEASE ALSO SHOW DISC'S PER 440.11 |
| | |
| | 16)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | 2002 NEC. |
| | |
| | 17)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 18)NOTE: PLEASE VERIFY SIZE OF SERVICE, |
| | INDICATES 200A SERVICE, HOWEVER LOAD |
| | CALCULATIONS AFTER ALL DERATING STILL |
| | INDICATES LOAD EXCEEDING RATING OF |
| | SERVICE.215.5/220.31 |
| | |
| | 19)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE SEE BOTH MISSING LEADING TO FLOOR |
| | ABOVE. |
| | |
| | 20)NOTE: PLEASE SEE GARAGE PLANS |
| | MENTIONS TO LT ABOVE ON SECOND LEVEL, |
| | HOWEVER NO 2ND FLR ELECTRICAL PLANS WERE |
| | SUBMITTED FOR REVIEW. |
| | PLEASE SUBMIT. 215.5 |
| | |
| | 21)NOTE: PLEASE SEE THERE ARE THREE |
| | GDO'S SHOWN ON PANEL SCHEDULE, HOWEVER |
| | PLANS ONLY INDICATES TWO DOORS AND TWO |
| | RECEPTS FOR GDO? PLEASE CORRELATE. |
| | |
| | 22)NOTE: PLEASE SEE PANEL SCHEDUL |
| | INDICATES A "WHIRLPOOL" TUB? YET, PLANS |
| | DO NOT SHOW ANY HOT TUB? GFI? ETC? |
| | |
| | 23)NOTE: PLEASE SEE E-1 AND M-SHEETS. |
| | THESE SHEETS ARE SIGNED WITH WHAT |
| | APPEARS TO BE A DIFFERENT SIGNATURE THAN |
| | OTHER SHEETS SIGNED BY ARCH. WE HAVE |
| | SIGNATURE ON FILE FOR MR. YECKES AND |
| | THESE SHEETS DO NOT MATCH. |
| | PLEASE SEE ONE SET OF THESE SHEETS ARE |
| | BEING RETAINED FOR FILE FOR THIS AND |
| | CODE COMPLIANCE REVIEW OF PLANS. |
| | PLEASE SEE THESE MAY BE REVIEWED BY THE |
| | FL BOARD OF ARCH'S. |
| | |
| | 24)NOTE: PLEASE SEE IF SERVICE IS INDEED |
| | LARGER THAN THE 200A SHOWN, PLEASE SEE |
| | 250.66 FOR SIZING OF GROUNDING ELECTRODE |
| | CONDUCTOR. |
| | |
| | 25)NOTE: PLEASE SEE DUE TO THE EXTEND OF |
| | CODE CORRECTIONS NEEDED ON PLANS, PLEASE |
| | SEE THERE MAY BE OTHER COMMENTS FOR |
| | FUTURE PLANS. |
| | ONE SET IS RETAINED. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |