2005-03-01 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PLANS/ PANEL
 SCHEDULE(S) AND RISER DIAGRAM.
 PLEASE SEE RISER MENTIONS 200A PANEL
 WITH SUB PANEL. NOTES MENTIONS 2-200A
 PANELS WITH 400A MCB AND 60A SUB POOL
 PANEL, HOWEVER PANELS AR BOTH SHOWN AS
 150A?
 PLEASE ALSO SEE #6'S FOR SUB PANEL, YET
 SUB PANEL IS 150A W/ 106A'S OF LOAD?
 PLEASE SEE PANEL "A" DOES NOT INDICATE
 ANY SUB-PANEL FEED?
 PLEASE SEE RISER ALSO SHOWS A 6/0 FOR
 EQUIPMENT GROUNDING CONDUCTOR.
 (MISPRINT)?
 ETC ETC.
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SHOW LOCATION OF ALL
 PANELS, DISCONNECTS ON PLANS.
 215.5
 PLEASE VERIFY IF GARAGE IS GOING TO HAVE
 A SUBPANEL?
  
 4)NOTE: PLEASE VERIFY IF FOOTER STEEL IS
 GOING TO BE BONDED FROM MAIN HOUSE FOR
 GROUNDING ELECTRODE SYSTEM.
 PER 250.50,250.32?
  
 5)NOTE: PLEASE LABEL PANELS ON RISER TO
 CORRELATE WITH PANELS.
  
 6)NOTE: PLEASE CORRELATE MECHANICAL
 PLANS WITH ELECTRICAL PLANS. MECH SHOWS
 BOTH HEAT-STRIPS AS 10KW, HOWEVER
 ELECTRICAL PLANS INDICATES 1-10KW AND
 1-5KW.
  
 7)NOTE: PLEASE SEE PANEL SCHEDULES,
 THERE ARE NUMEROUS ITEMS WHERE OCP, AWG
 AND KW/LOADS DO NOT MEET CODE.
 50A BRKR ON #12
 10A BRKR? W/ 5KW LOAD
 50A BRKR FOR SM APLL CIRCUITS.
 60A BRKR FOR 5KW HEAT.
 ETC ETC.
  
 8)NOTE: PLEASE SEE 210.11C1 AND 220.16
 FOR MIN TWO OR MORE SMALL APPLIANCE
 CIRCUITS.SEE PREVIOUS NOTE.
  
 9)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 10)NOTE: PLEASE SHOW ALL GARAGE RECEPTS
 AS GFI/GFI PROTECTED. 210.8
  
 11)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 MUST BE 20A AND #12
  
 12)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 THERE ARE NUMEROUS RECEPTS MISSING.
  
 13) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
 MISSING REAR, PLEASE ALSO INDICATE AS
 GFI.
  
 14)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 15)NOTE: PLEASE SEE MISSING A/C COND
 UNIT EQUIPMENT ON PLANS.
 PLEASE ALSO SHOW DISC'S PER 440.11
  
 16)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC.
  
 17)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 18)NOTE: PLEASE VERIFY SIZE OF SERVICE,
 INDICATES 200A SERVICE, HOWEVER LOAD
 CALCULATIONS AFTER ALL DERATING STILL
 INDICATES LOAD EXCEEDING RATING OF
 SERVICE.215.5/220.31
  
 19)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE BOTH MISSING LEADING TO FLOOR
 ABOVE.
  
 20)NOTE: PLEASE SEE GARAGE PLANS
 MENTIONS TO LT ABOVE ON SECOND LEVEL,
 HOWEVER NO 2ND FLR ELECTRICAL PLANS WERE
 SUBMITTED FOR REVIEW.
 PLEASE SUBMIT. 215.5
  
 21)NOTE: PLEASE SEE THERE ARE THREE
 GDO'S SHOWN ON PANEL SCHEDULE, HOWEVER
 PLANS ONLY INDICATES TWO DOORS AND TWO
 RECEPTS FOR GDO? PLEASE CORRELATE.
  
 22)NOTE: PLEASE SEE PANEL SCHEDUL
 INDICATES A "WHIRLPOOL" TUB? YET, PLANS
 DO NOT SHOW ANY HOT TUB? GFI? ETC?
  
 23)NOTE: PLEASE SEE E-1 AND M-SHEETS.
 THESE SHEETS ARE SIGNED WITH WHAT
 APPEARS TO BE A DIFFERENT SIGNATURE THAN
 OTHER SHEETS SIGNED BY ARCH. WE HAVE
 SIGNATURE ON FILE FOR MR. YECKES AND
 THESE SHEETS DO NOT MATCH.
 PLEASE SEE ONE SET OF THESE SHEETS ARE
 BEING RETAINED FOR FILE FOR THIS AND
 CODE COMPLIANCE REVIEW OF PLANS.
 PLEASE SEE THESE MAY BE REVIEWED BY THE
 FL BOARD OF ARCH'S.
  
 24)NOTE: PLEASE SEE IF SERVICE IS INDEED
 LARGER THAN THE 200A SHOWN, PLEASE SEE
 250.66 FOR SIZING OF GROUNDING ELECTRODE
 CONDUCTOR.
  
 25)NOTE: PLEASE SEE DUE TO THE EXTEND OF
 CODE CORRECTIONS NEEDED ON PLANS, PLEASE
 SEE THERE MAY BE OTHER COMMENTS FOR
 FUTURE PLANS.
 ONE SET IS RETAINED.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  