| 2005-02-24 00:00:00 | | | | | | | PROVISO | | | ~~~~~~~ | | | | | | PLEASE NOTE ARTICLE 230.70 CITY OF WEST | | | PALM BEACH AMMENDMENTS REQUIRE A | | | DISCONNECTING MEANS GROUPED WITH THE | | | METER IF MORE THAN 8' OF CONDUCTORS ARE | | | INSIDE THE HOUSE UNPROTECTED TO THE | | | FIRST BREAKER (OVERCURRENT PROTECTION). | | | IF THIS CONDITION EXISTS A DISCONNECT | | | BMUST BE ADDED AND THE PLANS REVISED | | | PRIOR TO INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|