| Plan Review Notes For Permit 05021123 |
| Permit Number |
05021123 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE ENGINEERS TITLE BLOCK MUST BE | | | SEALED AND HIS NAME SIGNED TO THE PLAN. | | | IF NOT TAKING RESPONSIBILITY FOR THE | | | PLAN, REMOVE ALL. THE PERSON TAKING | | | RESPONSIBILITY MUST COMPLY WITH 104.2.1 | | | FBC. AND ALL APPLICABLE STATUTES IF A | | | DESIGN PROFESSIONAL. | | | | | | 2} PLEASE SUBMIT A RISER DIAGRAM THAT | | | INDICATES ACTUAL CONDITIONS. THERE IS | | | ONE SERVICE WITH TWO METERS SHOWN ON THE | | | PLAN, AND TWO SEPERATE RISERS DEPICTED | | | ON THE RISER. PLEASE CORRELATE. | | | | | | 3} THE RISER SHOULD ALSO INDICATE | | | COMPLIANCE WITH WITH 250.32(GROUNDING) | | | AT THE HOUSE. | | | | | | 4} PLEASE SEE RECEPTACLES NEED TO BE | | | ADDED FOR 210.52(A)(1)&(2)THE GUEST | | | BEDROOM AND THE KITCHENETTE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|