| Plan Review Notes For Permit 05021053 |
| Permit Number |
05021053 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-21 00:00:00 | DENIED | | | | | | 1) THE BUILDING AREA TABLE ON T1 HAS A | | | HEADING THAT STATES 8-UNIT BUILDING. | | | | | | 2) THE ENERGY CALCULATIONS FOR THE 2215 | | | SQFT MID UNIT DOES NOT APPLY TO THIS | | | BUILDING. THE MID UNITS ARE 1448 SQFT. | | | PLEASE REMOVE THEM FROM THE PACKAGE. | | | | | | 3) THE UPLIFT GIVEN IN THE TRUSS | | | DRAWINGS EXCEEDS THE CAPACITY OF THE | | | CONNECTORS SPECIFIED FOR THE MG1 | | | TRUSSES. | | | | | | 4) THE ARROW ON SHEET S4 INDICATING THE | | | LOCATION OF THE HANGER SHOWN IN DETAIL | | | 10/S7 IS NOT CORRECT. CLARIFY THAT | | | DETAIL 10/S7 IS TO BE USED FOR THE (2) | | | MEMBER GR2 TRUSSES AS WELL AS THE (4) | | | MEMBER GR1 TRUSSES AT THE INTERIOR | | | WALLS. | | | | | | 5) THE ANCHOR SCHEDULE LISTS A SIMPSON | | | HDSA CONNECTOR. IS THIS A TYPO FOR A | | | HD5A CONNECTOR? INDICATE HOW THE UPLIFT | | | OF 8310# WAS DETERMINED FOR THIS | | | CONNECTOR. | | | | | | 6) SUBMIT THE MIAMI-DADE NOA | | | (INSTALLATION INSTRUCTIONS) FOR THE ONE | | | HOUR FIRE RATED GLASS BLOCK. | | | | | | 7) SUBMIT THE INSTALLATION INSTRUCTIONS | | | FOR THE ASPHALT ROOF SHINGLES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|