Plan Review Notes
Plan Review Notes For Permit 05021053
Permit Number 05021053
Review Stop B
Sequence Number 1
Notes
Date Text
2005-04-21 00:00:00DENIED
  
 1) THE BUILDING AREA TABLE ON T1 HAS A
 HEADING THAT STATES 8-UNIT BUILDING.
  
 2) THE ENERGY CALCULATIONS FOR THE 2215
 SQFT MID UNIT DOES NOT APPLY TO THIS
 BUILDING. THE MID UNITS ARE 1448 SQFT.
 PLEASE REMOVE THEM FROM THE PACKAGE.
  
 3) THE UPLIFT GIVEN IN THE TRUSS
 DRAWINGS EXCEEDS THE CAPACITY OF THE
 CONNECTORS SPECIFIED FOR THE MG1
 TRUSSES.
  
 4) THE ARROW ON SHEET S4 INDICATING THE
 LOCATION OF THE HANGER SHOWN IN DETAIL
 10/S7 IS NOT CORRECT. CLARIFY THAT
 DETAIL 10/S7 IS TO BE USED FOR THE (2)
 MEMBER GR2 TRUSSES AS WELL AS THE (4)
 MEMBER GR1 TRUSSES AT THE INTERIOR
 WALLS.
  
 5) THE ANCHOR SCHEDULE LISTS A SIMPSON
 HDSA CONNECTOR. IS THIS A TYPO FOR A
 HD5A CONNECTOR? INDICATE HOW THE UPLIFT
 OF 8310# WAS DETERMINED FOR THIS
 CONNECTOR.
  
 6) SUBMIT THE MIAMI-DADE NOA
 (INSTALLATION INSTRUCTIONS) FOR THE ONE
 HOUR FIRE RATED GLASS BLOCK.
  
 7) SUBMIT THE INSTALLATION INSTRUCTIONS
 FOR THE ASPHALT ROOF SHINGLES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  