2005-04-21 00:00:00DENIED
  
  
 1) THE AREA TABLE ON SHEET T1 IS
 INCORRECTLY LABELED 8 UNIT BUILDING.
  
 2) ENERGY CALCS. WERE SUBMITTED FOR A
 2215 SQFT MID UNIT. THE MID UNITS FOR
 THIS BUILDING ARE 1448 SQFT. PLEASE
 REMOVE THE INCORRECT CALCS.
  
 3) THE GR3 TRUSS IS INDICATED AS A TWO
 MEMBER TRUSS ON THE TRUSS DRAWINGS AND A
 FOUR MEMBER TRUSS ON S4 OF THE PLANS.
  
 4) THE CONNECTOR SCHEDULE ON S4 LISTS A
 SIMPSON HDSA. SHOULD THIS BE A HD5A?
 INDICATE HOW THE UPLIFT VALUE FOR THIS
 CONNECTOR WAS DETERMINED.
  
 5) SPECIFY THE CONNECTORS FOR THE GR2
 TRUSSES AT THE INTERIOR WALLS.
  
 6) CLARIFY THAT DETAIL 10/S7 IS FOR ROOF
 TRUSSES, IN ADDITION TO THE FLOOR
 TRUSSES.
  
 7) THE REQUIRED UPLIFTS GIVEN IN THE
 TRUSS DRAWINGS FOR THE MG1 TRUSSES
 EXCEED THE CAPACITY OF THE SPECIFIED
 CONNECTORS.
  
 8) SUBMIT THE MIAMI-DADE NOA
 (INSTALLATION INSTRUCTIONS) FOR THE ONE
 HOUR FIRE RATED GLASS BLOCK.
  
 9) SUBMIT THE INSTALLATION INSTRUCTIONS
 FOR THE ASPHALT ROOF SHINGLES.
  