| 2005-04-05 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.561-233-5025 |
| | |
| | 3.) NAILING FOR ROOF SHEATHING, 1-A6 AND |
| | BB-A3 (6 IN OC) IS NOT COMPLIANT FOR |
| | ZONE 3, FBC*TABLE 2306.1. |
| | |
| | 4.) ADDITIONAL FEES DUE TO VALUE |
| | ADJUSTMENT.1888SF X 76.96, 513 X 41.6, |
| | TOTAL OF 166640.SEE ATTACHED. |
| | |
| | 5.) WINDOW/DOOR BUCK DETAIL, A6, SHOWS |
| | ATTACHMENT INTO WOOD FRAMING. OTHER |
| | DETAILS SHOW THE CONSTRUCTION AS CBS. |
| | |
| | 6.) SPECIFY WINDOW AND DOOR SIZES. |
| | BEDROOM WINDOWS ARE TO COMPLY WITH |
| | EMERGENCY EGRESS REQUIREMENTS, |
| | FBC1005.4. |
| | |
| | 7.) SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |
| | |
| | 8.) PROVIDE REACTION LOADS, ROOF FRAMING |
| | PLAN. |
| | |
| | 9.) DOOR 2 BETWEEN LAUNDRY ROOM AND |
| | GARAGE IS TO BE SOLID CORE, |
| | FBC?13-403.1.ABCD. |
| | |
| | 10.) BB-A3 REFERS TO TRUSS PLAN FOR |
| | GIRDER DETAIL.THIS WAS NOT PROVIDED. |
| | NO CONNECTORS OR REACTION LOADS |
| | SPECIFIED FOR GIRDER CONNECTIONS. |
| | |
| | 11.) AA-A3, PORCH DETAILS, REFERS TO |
| | MECHANICAL PAGE. |
| | |
| | 12.) FLORIDA STATE PRODUCT APPROVAL DOES |
| | NOT APPEAR TO MATCH THE NOA PROVIDED. |
| | PROVIDE FLORIDA STATE PRODUCT APPROVAL |
| | AND CIRCLE WHICH PRODUCT YOU ARE USING |
| | |
| | 13.) THE SAME DATA SHEETS WERE PROVIDED |
| | FOR FL18 AND FL19.I CANNOT DETERMINE |
| | COMPLIANCE WITH FAC9B72. |
| | |
| | 14.) THE TWO SPEC SHEETS SUBMITTED FOR |
| | DOORS ARE FOR SINGLE DOORS.THE GLAZED |
| | DOORS ON THE PLAN ARE DOUBLE DOORS. |
| | |
| | 15.) THE PLAN SHOWS A PANEL DOOR FOR THE |
| | FRONT DOOR.THIS SERVES AS THE |
| | EMERGENCY MEANS OF ESCAPE FBC1005.4.5. |
| | IF THIS DOOR IS TO BE GLAZED, CHANGE THE |
| | PANEL DOOR NOTE ON THE PLAN AND INDICATE |
| | THE EMERGENCY MEANS OF ESCAPE. |
| | |
| | 16.) PRODUCT APPROVALS ALSO REQUIRED |
| | FOR: |
| | ROOF TILE |
| | SHUTTERS |
| | SINGLE HUNG WINDOWS |
| | OPAQUE DOOR |
| | |
| | PRODUCT APPROVALS NOT APPROVED PRIOR TO |
| | ISSUANCE WILL REQUIRE SEPARATE PERMITS |
| | FOR THOSE ITEMS. |
| | |
| | 17.) COMPLETE A HURRICANE SHUTTER |
| | INSTALLATION SCHEDULE, SEE ATTACHED. |
| | |
| | 18.) THIS PROPERTY IS IN THE FIRE |
| | DISTRICT.DECLARE A BUILDING TYPE |
| | FBC600.TYPE VI CONSTRUCTION NOT |
| | ALLOWED IN THE FIRE DISTRICT, FBC*102.1. |
| | |
| | 19.) SHOW COMPLIANCE WITH FBC TABLE 600 |
| | IN REGARDS TO FIRE RESISTANCE FOR |
| | EXTERIOR BEARING WALLS. |
| | |
| | 20.) PROVIDE DESIGN CRITERIA FOR THE |
| | TRUSSES, TCLL, TCDL, BCLL, BCDL.BCLL |
| | TO COMPLY WITH FBC TABLE 1604.1. |
| | |
| | 21.)SHOW ATTIC ACCESS LOCATION AND |
| | SIZE, FBC2309.6, 2309.7. |
| | |
| | 22.)32" CLEAR OPENING REQUIRED FOR THE |
| | FRONT DOOR, FBC TABLE 1004. |