| Plan Review Notes For Permit 05021030 |
| Permit Number |
05021030 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-02 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | CIRCUITS 1,3 AND 5 INCORRECTLY HAVE #14 | | | WIRE ON A 20AMP BREAKER.310.16. | | | | | | A SMOKE DETECTOR IS REQUIRED IN THE HALL | | | OUTSIDE OF THE BEDROOMS (2ND FL.) PER | | | 905.2.2 FBC. | | | | | | MAKE CORRECTIONS ON THE DRAWING AND | | | RESUBMIT PRIOR TO ROUGH ELECTRICAL | | | INSPECTION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|