| Plan Review Notes For Permit 05020997 |
| Permit Number |
05020997 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-25 00:00:00 | PROVISO: | | | 1.EXHAUST TERMINATION SHALL BE A | | | MINIMUM OF 10' ABOVE THE ADJOINING GRADE | | | AS WELL AS 10' FROM FRESH AIR INTAKE, | | | DOORS, WINDOWS, PARKING AREAS, PROPERTY | | | LINES AND ADJACENT BUILDINGS. | | | | | | 2.PROVIDE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS FOR THE FIRE WRAP ON THE | | | THE JOBSITE AT THE TIME OF INSPECTION. | | | | | | PLEASE NOTE:WELDS ARE TO BE | | | INSPECTED PRIOR TO COVERING WITH | | | WRAP. | | | | | | ADDITIONAL PERMIT REQUIRED FOR THE FIRE | | | SUPPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|