2006-08-08 00:00:00*** PROVISO ***
 1) RETURN AIR TRANSFER DUCT TO MASTER
 SUITE NEEDS TO BE 14", PER 2001 FBC/M
 601.4 .
 2) PROVIED COMBUSTION AND MAKE-UP AIR
 FOR GAS WATER HEATER, DUE TO CLOTHES
 DRYER EXHAUST, PER 2001 FBC/FG 614.5 AND
 304.4 .
 3) NO RETURN AIR GRILL PERMITED IN
 LAUNDRY ROOM DUE TO GAS APPLIANCES, PER
 2001 FBC/FG 304.4 AND 2001 FBC/R
 M1602.2(4) .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.